Liquiline CM442R/CM444R/CM448R
Operation
Hauser
101
Standard cleaning
Standard cleaning involves cleaning a sensor with compressed air, for instance, as performed
with the ion-selective sensor CAS40D (connection of the cleaning unit for CAS40D
Chemoclean
An example of the use of the "Chemoclean" function is the use of the CYR10 injector unit to clean
pH glass sensors. (CYR10 connection
Path: Menu/Setup/Additional functions/Cleaning/Cleaning 1 ... 4/Standard clean
Function
Options
Info
Cleaning time
5 to 600 s
Factory setting
10 s
Cleaning time ... Cleaning duration
The cleaning duration and interval depend on the
process and sensor. Determine the variables empirically
or based on experience.
Path: Menu/Setup/Additional functions/Cleaning/Cleaning 1 ... 4/Chemoclean
Function
Options
Info
Cleaning time
0 to 900 s
Factory setting
5 s
Cleaning duration
The cleaning duration, pre-rinse and post-rinse times
and the interval depend on the process and sensor.
Determine the variables empirically or based on
experience.
Prerinse time
0 to 900 s
Factory setting
0 s
Postrinse time
0 to 900 s
Factory setting
0 s