Technical data
Liquiline CM442R/CM444R/CM448R
152
Hauser
Ethernet and Modbus TCP
EtherNet/IP
15.4.2 Signal on alarm
Adjustable, as per NAMUR Recommendation NE 43
• In measuring range 0 to 20 mA (HART is not available with this measuring range):
Error current from 0 to 23 mA
• In measuring range 4 to 20 mA:
Error current from 2.4 to 23 mA
• Error current factory setting for both measuring ranges:
21.5 mA
15.4.3 Load
Max. 500
15.4.4 Linearization/transmission behavior
Linear
Signal encoding
IEEE 802.3 (ethernet)
Data transmission rate
10 / 100 MBd
Galvanic isolation
Yes
Connection
RJ45,
IP address
DHCP (default) or configuration via menu
Signal encoding
IEEE 802.3 (ethernet)
Data transmission rate
10 / 100 MBd
Galvanic isolation
Yes
Connection
RJ45
IP address
DHCP (default) or configuration via menu