Levelflex FMP56, FMP57 FOUNDATION Fieldbus
Integration into a FOUNDATION Fieldbus network
Hauser
73
In addition to the pre-instantiated blocks already mentioned, the following blocks can also
be instantiated:
• 5 Analog Input Blocks (AI)
• 2 Discrete Input Blocks (DI)
• 3 PID Blocks (PID)
• 3 Arithemetic Blocks (AR)
• 2 Signal Characterizer Blocks (SC)
• 5 Input Selector Blocks (IS)
• 3 Integrator Blocks (IT)
• 2 Analog Alarm Blocks (AAL)
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated. For instantiating blocks, see the appropriate Operating Instructions of the
configuration program used.
Hauser Guideline BA00062S.
The guideline provides an overview of the standard function blocks that are described
in FOUNDATION Fieldbus Specifications FF 890 - 894. It is designed to help operators
use the blocks implemented in the Hauser field devices.
9.4.2
Block configuration when device is delivered
DIAGNOSTIC
PID
ARITHMETIC
SIGNAL_CHAR
S
RESOURCE
ANALOG_INPUT_1
ANALOG_INPUT_2
DI
ADV_SETUP
DATA_TRANSFER
EXPERT_INFO
SERVICE_INFO
DISPLAY
INPUT_SELECTOR
INTEGRATOR
ANALOG_ALARM
EXPERT_CONFIG
SETUP
SERVICE_SENSOR
PV
SV
ESC
OPEN
OPEN
E
Device_01
F
mm
4841.000
A0017217
21
Block configuration when device is delivered
S
Sensor
PV Primary value: Level linearized
SV Secondary value: Distance
9.5
Assignment of the measured values (CHANNEL) in
an AI Block
The input value of an Analog Input Block is defined by the
CHANNEL
parameter.
Channel
Measured value
0
Uninitialized
89
Measured capacitance
144
EOP shift