Commissioning (block-based operation)
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
102
Hauser
Example
The
Highest severity / Configuration
group contains the messages
410: Data transfer
,
411: Up-/Download
,
435: Linearization
and
437: Configuration incompatible
. These
messages are no longer to be classified as
Failure (F)
but as
Function check (C)
.
1.
Use the FieldCare navigation window to navigate to the the following screen:
Expert
→ Communication → Field diagnostics → Alarm detection enable
.
2.
27
Default state of the "Fail Map" and "Check Map" columns
Look for the
Configuration Highest Severity
group in the
Fail Map
column and
deactivate the associated checkbox (A). Activate the respective checkbox in the
Check Map
column (B). Remember to confirm each change by pressing the Enter
key.