Important document information
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
12
Hauser
Ex-marking in case of connected FHX50 remote display
If the device is prepared for the remote display FHX50 (product structure: feature 030:
Display, Operation", option L or M), the Ex marking of some certificates changes according
to the following table
:
Feature 010 ("Approval") Feature 030 ("Display, Operation") Ex-marking
BE
L or M
ATEX II 1D Ex ta [ia] IIIC T
500
xx°C Da
BF
L or M
ATEX II 1/2 D Ex ta [ia Db] IIIC Txx°C Da/Db
BG
L or M
ATEX II 3G Ex nA [ia Ga] IIC T6 Gc
BH
L or M
ATEX II 3G Ex ic [ia Ga] IIC T6 Gc
B3
L or M
ATEX II 1/2G Ex d [ia] IIC T6 Ga/Gb,
ATEX II 1/2D Ex ta [ia Db] IIIC Txx°C Da/Db
IE
L or M
IECEx Ex ta [ia] IIIC T500 xx°C Da
IF
L or M
IECEx ta [ia Db] IIIC Txx°C Da/Db
IG
L or M
IECEx Ex nA [ia Ga] IIC T6 Gc
IH
L or M
IECEx Ex ic [ia Ga] IIC T6 Gc
I3
L or M
IECEx Ex d [ia] IIC T6 Ga/Gb,
IECEx Ex ta [ia Db] IIIC Txx°C Da/Db
1)
The marking of certificates not mentioned in this table are not affected by the FHX50.