Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
164
Hauser
Ramp at echo lost
Navigation
Setup → Advanced setup → Safety sett. → Ramp echo lost
Prerequisite
=
Ramp at echo lost
Description
Define the slope of the ramp in the case of a lost echo.
User entry
Signed floating-point number
Factory setting
0.0 %/min
Additional information
t
min
0%
100%
A
B
C
A0013269
A
Delay time echo lost
B
Ramp at echo lost (→ 164) (positive value)
C
Ramp at echo lost (→ 164) (negative value)
• The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously decreased until it
reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly increased until it
reaches 100%.
Blocking distance
Navigation
Setup → Advanced setup → Safety sett. → Blocking dist.
Description
Specify upper blocking distance UB.
User entry
0 to 200 m
Factory setting
• For rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
• For rod and rope probes above 8 m (26 ft): 0.025 * Sondenlänge
Additional information
Signals in the upper blocking distance are only evaluated if they have been outside the
blocking distance when the device was switched on and move into the blocking distance