Proline Promass 80
Technical data
Hauser
79
Flow values (example)
Repeatability
Design fundamentals
o.r. = of reading; 1 g/cc = 1 kg/l; T = medium temperature
• Mass flow and volume flow (liquid): ±0.10% o.r.
• Mass flow (gas): ±0.35% o.r.
• Density (liquid): ±0.00025 g/cc
• Temperature: ±0.25 °C ± 0.0025 · T °C; (±0.5 °F ± 0.0015 · (T–32) °F)
Influence of medium temperature
When there is a difference between the temperature for zero point adjustment and the process
temperature, the typical measured error of the sensor is ±0.0002% of the full scale value / °C
(±0.0001% of the full scale value/°F).
Influence of medium pressure
The table below shows the effect on accuracy of mass flow due to a difference between calibration
pressure and process pressure.
Turn down
Flow
Maximum measured error
[kg/h] or [l/h]
[lb/min]
[% o.r.]
250 : 1
72
2.646
2.50
100 : 1
180
6.615
1.00
25 : 1
720
26.46
0.25
10 : 1
1800
66.15
0.25
2 : 1
9000
330.75
0.25
o.r. = of reading; Design fundamentals
DN
[mm]
[inch]
[% o.r./bar]
8
3/8"
no influence
15
½"
no influence
25
1"
no influence
40
1 ½"
no influence
50
2"
–0.009
80
3"
–0.020
o.r. = of reading