background image

Products

Solutions

Services

Brief Operating Instructions

Deltapilot S FMB70

Hydrostatic level measurement

These Brief Operating Instructions are not a substitute for the

Operating Instructions pertaining to the device.
Detailed information about the device can be found in the

Operating Instructions and the additional documentation.
Available for all device versions via

• Internet: 

www.endress.com/deviceviewer

• Smartphone/tablet: 

Hauser Operations app

KA01020P/00/EN/17.22-00

71566247

2022-04-05

Содержание FMB70

Страница 1: ...substitute for the Operating Instructions pertaining to the device Detailed information about the device can be found in the Operating Instructions and the additional documentation Available for all...

Страница 2: ...rd cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 2 About this document 2 1 Document function The Brief Operati...

Страница 3: ...injury 2 2 2 Electrical symbols Ground connection A grounded terminal which as far as the operator is concerned is grounded via a grounding system Protective earth PE Ground terminals that must be con...

Страница 4: ...o perform this function and task Are authorized by the plant owner operator Are familiar with federal national regulations Before starting work read and understand the instructions in the manual and s...

Страница 5: ...e Use original spare parts and accessories from Endress Hauser only Hazardous area To eliminate a danger for persons or for the facility when the device is used in the hazardous area e g explosion pro...

Страница 6: ...can be identified in the following ways Nameplate specifications Extended order code with breakdown of the device features on the delivery note Enter serial number from nameplates in W M Device Viewe...

Страница 7: ...0 to 30 Nm 14 75 to 22 13 lbf ft 5 2 Mounting the device Due to the orientation of the Deltapilot S a zero point shift may occur i e when the vessel is empty the measured value does not display zero Y...

Страница 8: ...compensation and GORE TEX filter 1 free from contamination and water Do not clean or touch process membranes with hard or pointed objects The device must be installed as follows in order to comply wi...

Страница 9: ...toff device above the tapping point so that any condensate can flow into the process Pressure measurement in vapors Mount the Deltapilot S with the water pocket pipe above the tapping point Fill the w...

Страница 10: ...be tightened finger tight 2 Nm 1 48 lbf ft to the stop to ensure that the covers are securely seated and leak tight 6 Electrical connection 6 1 Connecting the device LWARNING Risk of electric shock If...

Страница 11: ...est Test 4 20mA Test 1 8 6 7 2 3 4 5 A0019989 1 Housing 2 Minimum supply voltage 10 5 V DC jumper is set as illustrated in the diagram 2 Minimum supply voltage 11 5 V DC jumper is set to the Test posi...

Страница 12: ...lectrical connection for devices with Harting plug Han7D B View of the plug in connection on the device Brown Green yellow Blue 6 1 2 Connection of devices with M12 plug p 21 PIN 2 1 3 4 A0011175 1 Si...

Страница 13: ...sion for non hazardous area 11 5 to 45 V DC 10 5 to 45 V DC Measuring the 4 to 20 mA test signal A 4 to 20 mA test signal can be measured via the positive and test terminal without interruption The mi...

Страница 14: ...10 5 11 U V 40 40 45 45 1282 1260 1500 1478 847 826 413 391 Test A A 1 RLmax U 11 V 23 mA 4 2 3 1 2 3 W RLmax RLmax U 1 V 2 23 mA 4 W RLmax U V RLmax U 1 V 0 5 23 mA 4 RLmax U 1 V 1 5 23 mA 4 W RLmax...

Страница 15: ...hnical data and instructions is included with all Ex systems as standard 7 Operation options Feature 20 Output operation in the order code provides you with information on the operating options availa...

Страница 16: ...connected To perform the corresponding function press the key or key combination for at least 3 s Press the key combination for at least 6 s for a reset Meaning Adopt lower range value A reference pre...

Страница 17: ...are displayed if the pressure is too high If a pressure that is greater than the maximum permitted pressure is present at the device messages E115 sensor overpressure and E727 sensor pressure error o...

Страница 18: ...mA value SET URV 100 0 corresponds to 20 mA value Operation must be unlocked The pressure applied must be within the nominal pressure limits of the sensor See information on the nameplate LEVEL SELECT...

Страница 19: ...g modes and guides you through the most important basic functions You specify which Quick Setup menu should be displayed with the setting in the MEASURING MODE parameter For a detailed parameter descr...

Страница 20: ...www addresses endress com 71566247 71566247...

Отзывы: