6 Configuring the Web Server
Fieldgate FXA720
38
Hauser
6.6
PROFIBUS setup
The
"PROFIBUS Setup"
function allows the user to set up communication and scanning on the
Fieldgate channels used by the web server.
Note!
• Where Fieldgate FXA720 is used in pass-through mode, the bus settings are made in the
PROFIBUS OPC server (ControlCare P View) or the CommDTM PROFIdtmDPV1 (FieldCare).
6.6.1 Communication settings
Procedure
1 If not already selected, press
"Switch to Specialist Mode"
and log in as administrator or
maintenance engineer.
2 Press
"Information & Configuration"
then
"PROFIBUS Setup"
The following screen appears (the number of channels depends on the Fieldgate):
3 Set up each channel by entering or ticking the parameters, see Table 6-9.
– The settings depend on the coupler or link in use, see the associated documentation.
– Press
"Send"
to download the parameters to the Fieldgate.