5 Getting Started
Hauser
27
5.3.4 Setting PROFIBUS DP bus parameters in P View
Note!
• If you are using P View and FieldCare together, the PROFIGate driver should be used for the
Fieldgate, see Section 5.3.2.
When Fieldgate FXA720 is used together with ControlCare P View, the PROFIBUS DP baudrate is
set in the PROFIBUS OPC server.
Procedure
1. Start the OPC server from the Control Panel and set it up as decribed in the P View manual.
Click on the Fieldgate node (Master) to open the configuration window.
2. In the
"Basic"
folder, set
– Station name
– Station address
– Baudrate
– Master Class 2
– If necessary check "Read All Slaves" and press "Quickstart" to scan the bus
3. In the
"Details"
folder, set
– Bus parameters
4. Press "OK" to store the parameters.