Diagnostics and troubleshooting
Deltabar PMD78B HART
66
Hauser
Diagnostic
number
Short text
Remedy instructions
Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
484
Failure mode simulation
active
Deactivate simulation
C
Alarm
485
Process variable
simulation active
Deactivate simulation
C
Warning
491
Current output
simulation active
Deactivate simulation
C
Warning
495
Diagnostic event
simulation active
Deactivate simulation
C
Warning
500
Process alert pressure
1. Check process pressure
2. Check configuration of process
alert
S
Warning
501
Process alert scaled
variable
1. Check process conditions
2. Check scaled variable
configuration
S
Warning
502
Process alert temperature 1. Check process temperature
2. Check configuration of process
alert
S
Warning
503
Zero adjustment
1. Check measuring range
2. Check position adjustment
M
Warning
Diagnostic of process
801
Supply voltage too low
Increase supply voltage
F
Alarm
802
Supply voltage too high
Decrease supply voltage
S
Warning
805
Loop current faulty
1. Check wiring
2. Replace electronics
F
Alarm
806
Loop diagnostics
1. Check supply voltage
2. Check wiring and terminals
M
Warning
807
No Baseline due to insuf.
volt. at 20 mA
Increase supply voltage
M
Warning
822
Sensor temperature out
of range
1. Check process temperature
2. Check ambient temperature
S
Warning
825
Operating temperature
1. Check ambient temperature
2. Check process temperature
S
Warning
841
Operating range
1. Check the process pressure
2. Check the sensor range
S
Warning
900
High signal noise
detected
1. Check impulse line
2. Check valve position
3. Check process
M
Warning
901
Low signal noise detected 1. Check impulse line
2. Check valve position
3. Check process
M
Warning
902
Min signal noise detected 1. Check impulse line
2. Check valve position
3. Check process
M
Warning
906
Out of range signal
detected
1. Process Information. No action
2. Rebuild baseline
3. Adapt signal range thresholds
S
Warning
1)
Diagnostic behavior can be changed.