Deltabar PMD78B HART
Commissioning
Hauser
55
If operation is locked via the operating menu, you can only unlock operation again via the
operating menu.
If operation is locked via the DIP switch, the key symbol appears on the local display.
Sealing the device
The housing cover is designed to be sealed for use in custody transfer.
A
B
A0038742
A
Single compartment housing
B
Dual compartment housing
9.8.2
Display operation - locking or unlocking
The key must be pressed for at least 2 seconds in order to lock or unlock the optical
keys. Display operation can be locked or unlocked in the dialog that appears.
Display operation locks automatically (except in the SIL wizard):
• After 1 minute on the main page if no key has been pressed
• After 10 minutes within the operating menu if no key has been pressed
9.8.3
Software locking or unlocking
If operation is locked by means of the DIP switch, you can only unlock operation again
by means of the DIP switch.
Locking via password in display / FieldCare / DeviceCare / SmartBlue
Access to the device configuration can be locked by assigning a password. The user role is
set to
Maintenance
option when the device is delivered to the customer. The device can be
fully configured with the
Maintenance
option user role. Afterwards, access to the
configuration can be locked by assigning a password. The lock sets the
Maintenance
option to the
Operator
option. The configuration can be accessed by entering the
password.
The password is defined under:
System
menu
User management
submenu
The user role can be changed from
Maintenance
option to
Operator
option under:
System → User management
Disabling the lock via the display / FieldCare / DeviceCare / SmartBlue
Once the password is entered, you can enable the configuration of the device as an
Operator
option by entering the password. The user role then changes to
Maintenance
option.
The password can be deleted if necessary in the
User management
submenu: System
→ User management