Deltabar PMD78B HART
Commissioning
Hauser
43
9
Commissioning
9.1
Preliminaries
The measuring range and the unit in which the measured value is transmitted correspond
to the data on the nameplate.
L
WARNING
The settings of the current output are relevant for safety!
This situation can result in product overflow.
‣
The setting for the current output depends on the setting in the
Assign PV
parameter.
‣
After changing the PV assignment, check the settings for the range (LRV and URV) and
reconfigure them if necessary.
L
WARNING
Process pressure above or below permitted maximum/minimum!
Risk of injury if parts burst! Warnings are displayed if the pressure is too high.
‣
If a pressure smaller than the minimum permitted pressure or greater than the
maximum permitted pressure is present at the device, a message is output.
‣
Only use the device within the sensor range limits!
9.1.1
As-delivered state
If no customized settings were ordered:
•
Assign PV
parameter
Pressure
option
• Calibration values defined by defined sensor nominal value
• The alarm current is set to min. (3.6 mA), (only if no other option was selected when
ordering)
• DIP switch to Off position
• If Bluetooth is ordered, then Bluetooth is switched on
9.2
Function check
Perform a function check before putting the measuring point into operation:
• "Post-installation check" checklist (see the "Installation" section)
• "Post-connection check" checklist (see the "Electrical connection" section)