6 Level Measurement
6.1 Start-up with the Universal HART Communicator DXR 275,
Commulog VU 260 Z or Commuwin II
Function check
The "Level linear", "Level cylindrical horizontal" and "Level manual" modes are selectable
via communication. In these modes, the current measured pressure value is
automatically converted to "%". To improve the display, other level, volume and weight
units can be selected using the "Unit after linearisation" parameter.
Your device can be checked for the advanced "level measurement" function as follows.
•
The sixth position of the order code has an M or N for the electronic version
Example: PMP 635-R 1 3L 1
M
1 A AF 1
•
The function "linearisation" (in line V3 of the operating matrix) can be selected.
•
Software No. given in V2H2:
– for devices with HART protocol: 6570
– for devices with INTENSOR protocol: 6950
Contents
This Chapter contains the following information:
•
Preparatory work for start-up
– Resetting to factory settings
– Setting damping
– Selecting pressure units
– Density correction
•
General description for setting the measuring range
– Adjustment with reference pressure
– Dry calibration:
•
Level adjustments
– Linearisation manual or semi-automatic
•
Other entry procedures
– Entering the 4 mA level value
– Selecting the output on error
– Securing the measuring point by locking
– Retrieval of measuring point information
Instructions on operating via the Commulog VU 260 Z
•
Pressing the
key calls up the entry mode – the line flashes.
•
To complete the entry the
key must again be pressed.
6 Level Measurement
Cerabar S
30
Hauser