4.2 Damping
τ
The damping affects the speed with which the output signal reacts to changes in
pressure.
Fixed damping values are assigned to the switch positions
0…7
.
They can be adjusted directly on the instrument.
(Fixed damping values for root functions are assigned to the switch positions 8…F. This
function cannot be selected for the Cerabar S.)
Damping-linear function:
switch positions 0…7
4.3 Locking/unlocking operation
Operation can be locked after commissioning. This protects the measuring point against
unwanted or unauthorised changes to parameters entered.
Keys
#
Key
Entry
1
Locking operation:
Simultaneously press +Z and –S once
1
Unlocking operation:
Simultaneously press +S and –Z once
Note!
Locking using the local keys, blocks operation over the local keys as well as all operations
via handheld terminals or Commuwin II. This is only released again by using the local
keys.
– –
+
Z
S
+
– –
+ +
Z
S
0
1234
5
6
7
8
9
AB
C
D
E
F
4...20
mA
Test
1
2
3
0 - 2
5 mba
r
0
1234
5
6
7
8
9
AB
C
D
E
F
BA187Y39
Position of
the damping
rotary switch
5
6
4
3
2
1
0
0 s
0 s
1 s
2 s
4 s
0.5 s
8 s
16 s
7
I
0
τ
2
τ
3
τ
63 %
100 %
τ
BA187Y40
The set damping can be read via communication
but not changed.
Damping can be adjusted via communication.
Note!
– –
+
Z
S
– –
+
Z
S
+
+
BA187Y4
8
Locking:
Simultaneously
press" +Z" and "–S"
Unlocking:
Simultaneously
press "–Z" and "+S"
Locking with keys has priority