Cerabar PMC51B HART
Commissioning
Hauser
19
1
4 5 6
7
2
3
A0043599
4
Segment display
1
Measured value
2
Bar graph proportional to the current output
3
Unit of measured value
4
Locked (symbol appears when the device is locked)
5
Bluetooth (symbol flashes if Bluetooth connection is active)
6
HART communication (symbol is displayed if HART communication is active)
7
Measured value output in %
8
Commissioning
8.1
Preliminaries
The measuring range and the unit in which the measured value is transmitted correspond to
the data on the nameplate.
L
WARNING
The settings of the current output are relevant for safety!
This situation can result in product overflow.
‣
The setting of the current output depends on the setting in the
Assign PV
parameter.
‣
After changing the
Assign PV
parameter, check the settings for the range (LRV and URV)
and reconfigure them if necessary.
L
WARNING
Process pressure above or below permitted maximum/minimum!
Risk of injury if parts burst! Warnings are displayed if the pressure is too high.
‣
If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, a message is output.
‣
Only use the device within the measuring range limits!
8.1.1
As-delivered state
If no customized settings were ordered: