Electrical connection
Cerabar PMC51B HART
10
Hauser
5.2.4
Level measurement
• Always mount the device below the lowest measuring point
• Do not install the device at the following positions:
• In the filling curtain
• In the tank outlet
• In the suction area of a pump
• At a point in the tank which could be affected by pressure pulses from the agitator
• Mount the device downstream from a shutoff device: the calibration and function check can
be carried out more easily
5.2.5
Closing the housing cover
NOTICE
Thread and housing cover damaged from dirt and fouling!
‣
Remove fouling (e.g. sand.) on the thread of the cover and housing.
‣
If you continue to encounter resistance when closing the cover, check the thread again for
fouling.
Housing thread
The thread of the electronics and connection compartment is coated with lubricant
varnish.
Avoid additional lubrication.
6
Electrical connection
6.1
Connecting requirements
6.1.1
Potential equalization
The protective ground on the device must not be connected. If necessary, the potential
matching line can be connected to the outer ground terminal of the device before the device is
connected.
1
A0045411
1
Ground terminal for connecting the potential matching line