Mounting

Cerabar PMC51B HART

8

Hauser

• Using a valve manifold allows for easy commissioning, installation and maintenance

without interrupting the process

• When mounting the device, establishing the electrical connection and during operation:

prevent the penetration of moisture into the housing

• Point the cable and plug downwards as much as possible to prevent moisture from entering

(e.g. rainwater or condensation)

5.1.3  

Installation instructions for thread

• Device with G 1 ½" thread:

Place the flat seal on the sealing surface of the process connection

Avoid additional strain on the membrane: do not seal the thread with hemp or similar

materials

• Device with NPT thread:

• Wrap Teflon tape around the thread to seal it

• Tighten the device at the hexagon bolt only; do not turn it by the housing

• When screwing in, do not overtighten the thread; tighten the NPT thread to the required

depth according to the standard

• For the following process connections, a tightening torque of max. 40 Nm (29.50 lbf ft) is

specified:

• Thread ISO228 G ½" with flush membrane

• Thread DIN13 M20 x 1.5 with flush membrane

• NPT 3/4" with flush membrane

Mounting devices with PVDF thread

L

WARNING

Risk of damage to process connection!

Risk of injury!

Devices with a PVDF thread must be installed with the mounting bracket provided!

PVDF is only intended for metal-free applications!

L

WARNING

Material fatigue from pressure and temperature!

Risk of injury if parts burst! The thread can become loose if exposed to high pressure and

temperature loads.

Check the leak-tight integrity of the thread regularly.

Use Teflon tape to seal the ½" NPT thread.

5.1.4  

Orientation

NOTICE

Damage to the device!

If a heated device is cooled during a cleaning process (e.g. by cold water), a vacuum develops

for a short time. As a result of this, moisture can enter the measuring cell via the pressure

compensation element (1).

Mount the device as follows.

Содержание Cerabar PMC51B

Страница 1: ...hey are not a substitute for the Operating Instructions pertaining to the device Detailed information about the device can be found in the Operating Instructions and the other documentation Available...

Страница 2: ...dress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 2 About this document 2 1 Document function The Brief Operating Instructions con...

Страница 3: ...tion on procedures and other facts which do not result in personal injury 2 2 2 Electrical symbols Ground connection Terminal for connection to the grounding system 2 2 3 Symbols for certain types of...

Страница 4: ...nnel The personnel for installation commissioning diagnostics and maintenance must fulfill the following requirements Trained qualified specialists must have a relevant qualification for this specific...

Страница 5: ...ure continued operational safety and reliability Carry out repairs on the device only if they are expressly permitted Observe federal national regulations pertaining to the repair of an electrical dev...

Страница 6: ...ce offers specific functions to support protective measures by the operator These functions can be configured by the user and guarantee greater in operation safety if used correctly An overview of the...

Страница 7: ...e installation Always firmly tighten the housing cover and the cable entries 1 Counter tighten the cable entries 2 Tighten the coupling nut 5 1 2 Installation instructions The devices are mounted acco...

Страница 8: ...tighten the NPT thread to the required depth according to the standard For the following process connections a tightening torque of max 40 Nm 29 50 lbf ft is specified Thread ISO228 G with flush membr...

Страница 9: ...pping point so that any condensate can flow into the process 5 2 2 Pressure measurement in vapors A water pocket pipe reduces the temperature to almost the ambient temperature The defined water column...

Страница 10: ...OTICE Thread and housing cover damaged from dirt and fouling Remove fouling e g sand on the thread of the cover and housing If you continue to encounter resistance when closing the cover check the thr...

Страница 11: ...thread The thread of the electronics and connection compartment is coated with lubricant varnish Avoid additional lubrication 6 2 1 Supply voltage Ex d Ex e non Ex supply voltage 10 5 to 35 VDC Ex i...

Страница 12: ...tched on 6 2 2 Terminals Supply voltage and internal ground terminal 0 5 to 2 5 mm2 20 to 14 AWG External ground terminal 0 5 to 4 mm2 20 to 12 AWG 6 2 3 Cable specification Protective ground or groun...

Страница 13: ...deration Maximum 6 V with a communication resistor of 250 6 2 5 Overvoltage protection Devices without optional overvoltage protection Equipment from Endress Hauser fulfills the requirements of the pr...

Страница 14: ...with IEC EN 61010 The cables must be adequately insulated with due consideration given to the supply voltage and the overvoltage category The connecting cables must offer adequate temperature stabilit...

Страница 15: ...onnection compartment 1 Positive terminal 2 Negative terminal 3 Internal ground terminal 6 2 8 Cable entries 1 2 A0045413 1 Cable entry 2 Dummy plug The type of cable entry depends on the device versi...

Страница 16: ...ation of moisture into the device Devices with valve plug 2 1 A B BU BN GNYE 2 1 3 A0023097 3 BN brown BU blue GNYE green yellow A Electrical connection for devices with valve connector B View of the...

Страница 17: ...sport protection IP22 TYPE 2 Cable 5 m IP66 68 TYPE 4X 6P pressure compensation via cable Valve plug ISO4400 M16 IP65 TYPE 4X HAN7D plug 90 degrees IP65 NEMA Type 4X M12 plug When housing is closed an...

Страница 18: ...switch for locking and unlocking the device The setting of the DIP switches has priority over the settings made via other operation methods e g FieldCare DeviceCare 7 2 Access to the operating menu v...

Страница 19: ...plate LWARNING The settings of the current output are relevant for safety This situation can result in product overflow The setting of the current output depends on the setting in the Assign PV parame...

Страница 20: ...ng tool See the description of the operating tool 8 5 Configuring the measuring device 8 5 1 Commissioning with keys on the electronic insert The following functions are possible via the keys on the e...

Страница 21: ...ion offset Resetting the device Press and hold the Zero and Span keys simultaneously for at least 12 s 8 5 2 Commissioning with the commissioning wizard In FieldCare DeviceCare 1 SmartBlue and on the...

Страница 22: ...easured value when the vessel is empty or partly filled the measured value is not zero Perform a position adjustment if necessary In the Assign PV parameter the Pressure option must be selected factor...

Страница 23: ...ressure shifts in the measured value when the vessel is empty or partly filled the measured value is not zero Perform position adjustment if necessary B 450 mbar 1000 l A 50 mbar 0 l V l 1000 0 50 p m...

Страница 24: ...ure value 2 4 Enter the volume value for the upper calibration point via the Scaled variable value 2 parameter 1000 l 264 gal Menu path Application Sensor Scaled variable Scaled variable value 2 Resul...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...www addresses endress com 71582834 71582834...

Отзывы: