Commissioning
Cerabar PMC51B HART
24
Hauser
3. Enter the pressure value for the upper calibration point via the
Pressure value 2
parameter: 450 mbar (6.75 psi)
Menu path: Application → Sensor → Scaled variable → Pressure value 2
4. Enter the volume value for the upper calibration point via the
Scaled variable value 2
parameter: 1
000 l (264 gal)
Menu path: Application → Sensor → Scaled variable → Scaled variable value 2
Result: The measuring range is set for 0 to 1
000 l (0 to 264 gal). Only the
Scaled variable
value 1
parameter and
Scaled variable value 2
parameter are set with this setting. This
setting has no effect on the current output.