Commissioning
Hauser
21
3. When the LED lights up briefly, the pressure present has been accepted for the lower
range value.
Setting the upper range value (pressure or scaled variable)
1. The desired pressure for the upper range value is present at the device.
2. Press the "Span" key for at least 3 s.
3. When the LED lights up briefly, the pressure present has been accepted for the upper
range value.
4. Does the LED on the electronic insert not light up?
Applied pressure has not been accepted for upper range value.
Wet calibration is not possible if the
Scaled variable
option has been selected in
the
Assign PV
parameter and the
Table
option has been selected in the
Scaled
variable transfer function
parameter.
Checking the settings (pressure or scaled variable)
1. Press the "Zero" key briefly in order to display the lower range value.
2. Press the "Span" key briefly in order to display the upper range value.
3. Press the "Zero" and "Span" keys simultaneously in order to display the calibration offset.
Resetting the device
‣
Press and hold the "Zero" and "Span" keys simultaneously for at least 12 s.
8.5.2
Commissioning with the commissioning wizard
In FieldCare, DeviceCare
, SmartBlue and on the display, the
Commissioning
wizard is
available to guide the user through the initial commissioning steps. Commissioning is also
possible via AMS or PDM.
1. Connect the device with FieldCare or DeviceCare.
2. Open the device in FieldCare or DeviceCare.
The dashboard (homepage) of the device is displayed:
3. In the
Guidance
menu, click the
Commissioning
wizard to open the wizard.
4. Enter the appropriate value in each parameter or select the appropriate option. These
values are written directly to the device.
5. Click "Next" to go to the next page.
6. Once all the pages have been completed, click "End" to close the
Commissioning
wizard.
If the
Commissioning
wizard is cancelled before all the necessary parameters have been
configured, the device may be in an undefined state. In such situations, it is advisable to
reset the device to the factory default settings.