Function parameter schedule graph
24
supervision parameter
selection
1: Output frequency
2: Output current
3: Output voltage
4: DC bus bar voltage
5: Motor speed
6: Heat sink temperature
7: Run time
8: Accumulative run time
9: Input terminal status
10: Output terminal status
11: Analog input VCI/PID provision
12: Analog input CCI/PID feedback
13: Reserved
14: Reserved
F3.29 PID feedback signal
loss detection
0.0
~
9.999s 0.1s
0.0s
○
F3.30 Failure relay TA, TB,
TC function selection
0: Inverter running
(
RUN
)
1: Frequency arriving signal
(
FAR
)
2: Frequency level detect signal
(
FDT1
)
3: Reserved
4: Overload warning alarm signal
(
OL
)
5: Output frequency reach high limit
(
FHL
)
6: Output frequency reach low limit
(
FLL
)
7: Inverter under voltage blockage stop (LU)
8: External failure stop-running
(
EXT
)
9: Inverter zero speed running
10: PLC running
11: Simple PLC section running finished
12: PLC finish a cycle running
13: Reserved
14: Inverter ready to run(RDY)
15: Inverter failure
16: Traverse high and low limit restriction
17: Interior counter reach final value
18: Interior counter reach specified value
19: Set run time arriving
20: Intervior timing arriving
21: Reserved
22: FWD running
23: REV running
24: Reserved
1 15
○
F3.31 Reserved
F4
-
simple PLC function parameter group
Function
code
Name
Set range
Unit
Factory
default
Modifi
cation
F4.00 Simple
PLC
running setting
LED unit digit:
0: No action
1: Stop after single circulation
2: Keep final value after single circulation
3: Consecutive circulation
1 0000 ×
ENC