Function parameter schedule graph
23
2: CCI analog provision
3: Keypad potentiometer provision
F3.02
Feedback
channel selection
0: Reserved
1: CCI analog input
1 0
○
F3.03
Specified value
digital setting
0.000
~
9.999V (SetF3.00=1
,
F3.21=9.999)
0.001 0.200
○
Target pressure
value setting
0.000
~
F3.21Mpa (set F3.00=2)
0.001 0.200
○
F3.04 Minimum
specified value
0.0
~
Maximum specified value; percentage
relative to 10.00V
0.1(%) 0.0(%)
○
F3.05 Feedback
value
responding to
minimum specified
value
0.0(%)
~
100.0(%)
0.1(%) 0.0(%)
○
F3.06 Maximum specified
Minimum specified value
~
100.0
(
%
)
0.1(%)
100.0(%)
○
F3.07 Feedback
value
responding to
maximum specified
value
0.0%
~
100.0%
0.1(%) 100.0(%)
○
F3.08 Proportion
gain
Kp
0.000
~
9.999 0.001
0.150
○
F3.09 Integral gain Ki
0.000
~
9.999 0.001
0.150
○
F3.10 Differential
gain
Kd 0.000
~
9.999 0.001
0.000
○
F3.11 Sampling
cycle
T
0.01
~
1.00s 0.01s
0.10s
○
F3.12 Deviation
margin
0.0
~
20.0(%) Relative to the percentage of set
value.
0.1(%) 2.0(%)
○
F3.13 Integral separation PID
adjusting threshold
0.0
~
100.0(%) 0.1(%)
100.0(%)
○
F3.14 Closed-loop
preset
frequency
0
~
upper limit frequency
0.01Hz 0.00Hz
○
F3.15 Closed-loop
preset
frequency holding
time
0.0
~
6000.0s 0.1s
0.0s
○
F3.16 Sleep
frequency
threshold
0.00
~
400.00Hz 0.01Hz
30.00Hz
○
F3.17 Revival
pressure
threshold
0.000
~
F3.21Mpa 0.001
0.150
○
F3.18 Sleep
delay
time
0.0
~
6000.0s 0.1s
0.0s
○
F3.19 Revival delay time
0.0
~
6000.0s 0.1s
0.0s
○
F3.20 Reserved
F3.21 Long-distance pressure
meter range
0.000
~
9.999Mpa 0.001
1.000
○
F3.22 Reserved
F3.23 Reserved
F3.24 Reserved
F3.25 Reserved
F3.26 Water
supply
supervision parameter
display
0: C-11reserved, C-12 display CCI voltage value
1: C-11, C-12 display PID specified pressure and
feedback pressure
1 0
○
F3.27 Closed-loop
adjusting
characteristic
0: Forward function
1: Reverse function
1 0
○
F3.28 LED initial
0: Set frequency
1
1
○
ENC