Trouble shooting
34
P.OFF Under voltage Under voltage
check spot input voltage
5.2 Failure record lookup
This series inverter can record the latest 6 times failure code and inverter run
parameter of the last fault, to search these information can contribute to finding out
fault cause.
Fault information is all stored in Fd group parameter
,
please enter into Fd group
parameter to search information by referring to keypad operation method.
Code
Content
Code
Content
Fd.00
Previous 1 time fault record
Fd.08
Output current at previous 1
time fault
Fd.01
Previous 2 time fault record
Fd.09
Output volt. at previous 1 time
fault
Fd.02
Previous 3 time fault record
Fd.10
DC bus-bar volt. at previous 1
time fault
Fd.03
Previous 4 time fault record
Fd.11
Load motor speed at previous
1 time fault
Fd.04
Previous 5 time fault record
Fd.12
Module temp. at previous 1
time fault
Fd.05
Previous 6 time fault record
Fd.13
Input terminal state at
previous 1 time fault
Fd.06
Set freq. at previous 1 time
fault
Fd.14
Accum. runtime at previous 1
time fault
Fd.07
Output freq. at previous 1
time fault
5.3 Fault reset
To resume normal running when fault occur in the inverter, you can choose any
kinds of operation as follows:
(1) Set any one terminal of X1~X2 to external RESET input (F5.00~F5.01=10),
turn it off after connected to COM terminal.
(2) When fault code is displayed, Press key after restoration is confirmed
(3) Cut off power supply.
STOP
RESET
⑴
Before reset you must find out fault cause downright and eliminate it, otherwise
may cause permanent damage to the inverter..
⑵
Before reset you must find out fault cause downright and eliminate it, otherwise
may cause permanent damage to the inverter.
⑶
Reset should be delay for 5 minutes after overload, overheat protection action.
!
ENC