Function parameter schedule graph
18
4
Function parameter schedule graph
4.1 Symbol description
×
----
Parameter can’t be changed in process of running
○
----
Parameter can be changed in process of running
* ----
Read-only parameter, unmodifiable
4.2 Function parameter schedule graph
F0
-
Basic run function parameter group
Function
code
Name
Set range
Unit
Factory
default
Modifi
-cation
F0.00 Frequency
input
channel selection
0: Keypad analog potentiometer setting
1: Keypad digital setting
2: Terminal UP/DOWN adjust setting (stored
after power off)
3: Serial port setting
4: Reserved
5: CCI analog setting (CCI-GND)
6: Reserved
7: Reserved
8: Combination setting
9: Terminal UP/DOWN adjust setting (not stored
after power off)
10: Provision series port (stored after power off )
11: Remain
1 1
○
F0.01 Frequency digit setting Lower limit frequency
~
upper limit frequency
0.01Hz 50.00Hz
○
F0.02 Run command channel
selection
0: Keyboard run control
1: Terminal run command control (Keyboard
STOP command ineffective)
2: Terminal run command control(Keyboard
STOP command effective)
3: Serial port run command control(Keyboard
STOP command ineffective)
4: Serial port run command control(Keyboard
STOP command effective)
1 0
○
F0.03 Run direction setting
LED Units digit: 0: Forward run
1: Reverse run
LED Tens digit: 0: Reverse run allowed
1: Reverse run banned
LED Hundreds digit: REV/JOG key selection
0: As reverse run key
1: Reverse run banned
1 100
○
F0.04 Acce/Dece
mode
selection
0: Linear accelerating decelerating mode
1: S curve accelerating decelerating mode
1 0 ×
F0.05 S curve start section
time
10.0
(
%
)~
50.0
(
%
)
(
Acce/Dece time
)
F0.05+F0.06
≤
90
(%)
0.1(%) 20.0(%)
○
F0.06 S curve risetime
10.0
(
%
)~
70.0
(
%
)
(
Acce/Dece time
)
F0.05+F0.06
≤
90
(
%
)
0.1(%) 60.0(%)
○
ENC