intermittent pilot control sYstem troUbleshooting
PRoBLem oBSeRVeD
PoSSIBLe CAUSe
CoRReCTIVe meASURe
Gas odor during setup
Gas Leak
What to do if YoU smell gas
do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Leave the building immediately.
immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
if you cannot reach your gas supplier,
call the fire department.
Gas odor before first ignition
Gas Leak
Fireplace is
“
on
”
but no flame and pilot is
not trying to light
Gas Line Valve turned
“
off
”
Turn shutoff valve to
“
open
”
position
Control module in
“
lockout
”
Turn fireplace
“
off
”
and then back
“
on
”
Pilot continues to spark when pilot is lit.
Not enough gas to pilot
Wait for pilot flame to strengthen
Low Gas Pressure
Check pressures. See page 12.
Pilot igniter/sensor is dirty
Clean pilot. See maintenance page 79.
Pilot not grounded well
Check ground connections
Draft in firebox
Vent restrictor not installed
Pilot sensor has been bent
Replace pilot
Pilot will not ignite, or will not stay lit
Pilot igniter/sensor is dirty
Clean flame sensor and pilot igniter. See
maintenance page 79.
Pilot not grounded well
Check ground connections
Sensor Wire loose
Check sensor wire terminals
Gas pressure incorrect
Adjust gas pressure
Pilot Gas Line bent or kinked
Replace pilot tube
Faulty pilot, Sensor bent
Replace Pilot
Faulty valve
Replace Valve
Burner takes too long to fully light
Low gas pressure
Check gas supply pressure
Clogged or dirty carryover/burner ports
Clean ports
Blocked orifice
Check orifice opening
Faulty valve
Replace valve
Burner does not light but pilot remains on
Low gas pressure
Check gas supply pressure
Clogged or dirty burner ports
Clean burner ports
Blocked orifice
Check orifice opening
Loose wire connections
Check valve/control module connections
Faulty pilot
Replace pilot
Faulty valve
Replace valve
Burner lights but does not stay lit while
pilot remains on
Low gas pressure
Check gas supply pressure
Loose sensor wire
Check wire connection
Faulty valve
Replace valve
Faulty pilot or thermocouple
Replace Safety pilot
Clogged or dirty burner ports
Clean burner ports
(For fireplace equipped with optional ther
-
mostat or thermostat remote) Room tem
-
perature is higher than thermostat setting
move (optional) remote away from fire
-
place
Set higher temperature on (optional)
remote/thermostat
(optional) Remote control batteries failing
Replace batteries in remote transmitter
and receiver
Содержание MILLIVOLT DVCD32FP30
Страница 47: ...38712 2 0719 Page 47 7 Tuck Log G under Log C and onto pin of Log B LOG PLACEMENT for DVCD32 fireplaces...
Страница 48: ...38712 2 0719 Page 48 Log placement is complete LOG PLACEMENT for DVCD32 fireplaces...
Страница 57: ...38712 2 0719 Page 57 LOG PLACEMENT For DVCD36 fireplaces Log placement is complete...
Страница 67: ...38712 2 0719 Page 67 Log placement is complete LOG PLACEMENT for DVCD42 fireplaces...
Страница 93: ...38712 2 0719 Page 93 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...
Страница 94: ...38712 2 0719 Page 94 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...
Страница 95: ...38712 2 0719 Page 95 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...