CG Drives & Automation 01-7491-01r0
Applications
61
6.
Applications
This chapter contains tables giving an overview of many
different applications/duties in which it is suitable to use AC
drives from CG Drives & Automation. Further on you will
find application examples of the most common applications
and solutions.
6.1
Application overview
6.1.1 Pumps
6.1.2 Fans
Challenge
Emotron FDU solution
Menu
Dry-running, cavitation and overheating damage
the pump and cause downtime.
Pump Curve Protection detects deviation.
Sends warning or activates safety stop.
411–419, 41C1– 41C9
Sludge sticks to impeller when pump has been
running at low speed or been stationary for a
while. Reduces the pump’s efficiency.
Automatic pump rinsing function: pump is set to
run at full speed at certain intervals, then return
to normal speed.
362–368, 560, 640
Motor runs at same speed despite varying
demands in pressure/flow. Energy is lost and
equipment stressed.
PID continuously adapts pressure/flow to the
level required. Sleep function activated when
none is needed.
320, 380, 342, 354
Process inefficiency due to e.g. a blocked pipe, a
valve not fully opened or a worn impeller.
Pump Curve Protection detects deviation.
Warning is sent or safety stop activated.
411–419, 41C1–41C9
Water hammer damages the pump when
stopped. Mechanical stress on pipes, valves,
gaskets, seals.
Smooth linear stops protect the equipment.
Eliminates need for costly motorized valves.
331–336
Challenge
Emotron FDU solution
Menu
Starting a fan rotating in the wrong direction can
be critical, e.g. a tunnel fan in event of a fire.
Fan is started at low speed to ensure correct
direction and proper function.
219, 341
Draft causes turned off fan to rotate the wrong
way. Starting causes high current peaks and
mechanical stress.
Motor is gradually slowed to complete stop
before starting. Avoids blown fuses and
breakdown.
219, 33A, 335
Regulating pressure/flow with dampers causes
high energy consumption and equipment wear.
Automatic regulation of pressure/flow with motor
speed gives more exact control.
321, 354
Motor runs at same speed despite varying
demands in pressure/flow. Energy is lost and
equipment stressed.
PID continuously adapts to the level required.
Sleep function is activated when none is
needed.
320, 380, 342, 354
Process inefficiency due to e.g. a blocked filter, a
damper not fully opened or a worn belt.
Load Curve Protection detects deviation.
Warning is sent or safety stop activated.
411–419, 41C1–41C9
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......