CG Drives & Automation 01-7491-01r0
Functional description
117
•
Communication command Run and one or both of
RunR or RunL are set.
•
Function enabled (Trip or Warning) in menu "[2647]
CPportFMode"
•
No communication on the control panel port for
"[2648] CPportFTime" X seconds.
Control Panel port Fault Mode [2647]
Control Panel port Fault Time [2648]
Ethernet [265]
Settings for Ethernet module (Modbus/TCP, Profinet IO).
For further information, see the Fieldbus option manual.
IP Address [2651]
MAC Address [2652]
Defines mapping for additional process values. For further
information, see the Fieldbus option manual.
FB S1/Wr1 - FB S8/Wr8 [2661]-[2668]
Used to create a block of parameters which can be written
via communication.
FB S9/Rd1 - FB S16/Rd8 [266A]-[266G]
Used to create a block of parameters which can be read via
communication.
Sub menus showing status of Fieldbus parameters. Please see
the Fieldbus manual for detailed information.
2647
CPportFMode
Default:
Trip
Off
0
No supervision of the control panel.
Trip
1
The drive will trip after time set in
parameter [2648] if control panel is
removed.
Warning
3
The drive will give a warning after time
set in parameter [2648] if the control
panel is removed.
2648
CPportFTime
Default:
10.0 s
Range:
0.1 s - 15.0 s
NOTE: The Ethernet module must be re-booted to
activate the below settings. For example by toggling
parameter [261]. Non-initialized settings indicated by
flashing display text.
2651
IP Address
Default:
0.0.0.0
2652
MAC Address
Default:
An unique number for the Ethernet
module.
2653
Subnet Mask
Default:
0.0.0.0
2654
Gateway
Default:
0.0.0.0
2655
DHCP
Default:
Off
Selection:
On/Off
2661
FB S1/Wr1
Default:
0
Range:
0-65535
266A
FB S9/Rd1
Default:
0
Range:
0-65535
NOTE: For Modbus all 16 fieldbus mappings can be
used either as read or write. Configuration of register
map is made menu [2661]-[266G] or Modbus range
42801-42816. Register read/write access is made in
Modbus range 42821-42836.
269
FB Status
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......