CG Drives & Automation 01-7491-01r0
169
Analogue Comparator 1, Level Low [6113]
Sets the analogue comparator low level, with unit and range
according to the selected value in menu [6111].
Analogue Comparator 1, Type [6114]
Selects the analogue comparator type, i.e. Hysteresis or
Window type. See fig. 140 and fig. 141.
Analogue Comparator 1, Polarity [6115]
Selects how the selected value in [6111] should be handled
prior to the analogue comparator , i.e. as absolute value or
handled with sign. See fig. 140
Example
See fig. 140 and fig. 141 for different principle
functionality of comparator features 6114 and 6115.
Fig. 140 Principle functionality of comparator features for
“Type [6114] = Hysteresis ”and “Polar [6115]”.
Table 39
Comments to fig. 139 regarding Window selection.
No.
Description
Window
1
The reference signal passes the Level LO
value from below (signal inside Window
band), the comparator CA1 output is set
high.
2
The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
3
The reference signal passes the Level HI
value from above (signal inside Window
band), the comparator CA1 output is set
high.
4
The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
5
The reference signal passes the Level LO
value from below (signal inside Window
band), the comparator CA1 output is set
high.
6
The reference signal passes the Level HI
value from below (signal outside Window
band),the comparator CA1 is reset, output is
set low.
7
The reference signal passes the Level HI
value from above (signal inside Window
band), the comparator CA1 output is set
high.
8
The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
6113
CA1 LevelLO
Default:
200 rpm
Range:
Range as [6112].
6114
CA1 Type
Default:
Hysteresis
Hysteresis
0
Hysteresis type comparator
Window
1
Window type comparator
6115
CA1 Polar
Default:
Unipolar
Unipolar
0
Absolute value of [6111] used
Bipolar
1
Signed value of [6111] used
Type [6114]= Hysteresis
[6115] Unipolar
[6115] Bipolar
[6115] Bipolar
[6115] Bipolar
[6112] HI > 0
[6113] LO > 0
[6112] HI > 0
[6113] LO > 0
[6112] HI > 0
[6113] LO < 0
[6112] HI < 0
[6113] LO < 0
An.Value
[6111]
An.Value
[6111]
An.Value
[6111]
An.Value
[6111]
CA1
CA1
CA1
CA1
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......