CG Drives & Automation 01-7491-01r0
155
With AnIn1 Function Max the physical maximum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511]. See table
35.
AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5136].
Example:
Process sensor is a sensor with the following specification:
Range:
0–3 bar
Output:
2–10 mA
Analogue input should be set up according to:
[512] AnIn1 Setup = User mA
[5131] AnIn1 Min = 2 mA
[5132] AnIn1 Max = 10 mA
[5134] AnIn1 Function Min = User-defined
[5135] AnIn1 VaMin = 0.000 bar
[5136] AnIn 1 Function Max = User-defined
[5137] AnIn1 VaMax = 3.000 bar
If the input signal is unstable (e.g. fluctuation reference
value), the filter can be used to stabilize the signal. A change
of the input signal will reach 63% on AnIn1 within the set
AnIn1 Filter time. After 5 times the set time, AnIn1 will
have reached 100% of the input change. See fig. 134.
Fig. 134
Parameter for enable/disable analogue input selection via
digital inputs (DigIn set to function AnIn Select).
5136
AnIn1 FcMax
Default:
Max
Min
0
Min value
Max
1
Max value
User
defined
2
Define user value in menu [5137]
5137
AnIn1 VaMax
Default:
0.000
Range:
-10000.000 – 10000.000
NOTE: With AnIn Min, AnIn Max, AnIn Function Min
and AnIn Function Max settings, loss of feedback
signals (e.g. voltage drop due to long sensor wiring)
can be compensated to ensure an accurate process
control.
5138
AnIn1 Oper
Default:
Add+
Add+
0
Analogue signal is added to selected
function in menu
[
511
].
Sub-
1
Analogue signal is subtracted from
selected function in menu
[
511
].
5139
AnIn1 Filt
Default:
0.1 s
Range:
0.001 – 10.0 s
513A
AnIn1 Enabl
Default:
On
On
0
AnIn1 is always active
!DigIn
1
AnIn1 is only active if the digital input is low.
DigIn
2
AnIn1 is only active if the digital input is
high.
AnIn change
100%
63%
Original input signal
Filtered AnIn signal
T
5 X T
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......