180
CG Drives & Automation 01-7491-01r0
11.6.7
Group 670 if only available if the drive is equipped with a
4-line type Control panel (incl. RTC).
There are two Clock functions, Clock 1 and Clock 2. Each
clock with separate settings for Time on, Time Off, Date on,
Date Off and Weekday. These clocks can be used for
activating/deactivating desired functions via Relay, digital
output or Virtual I/O (For example creating start and stop
commands).
The time, date and weekday for clock 1 are set in these
submenus.
Time when the clock 1 output signal (CLK1) is activated.
Clock 1 Time Off [6812]
Time when the clock 1output signal (CLK1) is deactivated.
Date when the clock 1 output signal (CLK1) is activated.
Clock 1 Date Off [6814]
Date when the clock output signal (CLK1) is deactivated.
Note that if “Clk1DateOff” is set to an earlier date than
“Clk1DateOn”, the result will be that the clock is not
deactivated at the set date.
Clock 1 Weekday [6815]
Weekdays when the clock function is active. Having entered
the editing mode, select or unselect the desired weekdays
with the cursor using the PREV and NEXT keys on the
control panel. Confirm by pressing ENTER. Exit the editing
mode and the activated weekdays will be viewed in the menu
display. The deactivated weekdays are replaced by a dash
mark “-” (e.g. “MTWTF - -”).
Example 1:
The output CLK1 shall be active Mondays to Fridays on
working hours, e.g. 08:00-17:00. This signal is used to start
e.g. a fan with virtual I/O.
Example 2:
The output CLK1 shall be active on weekends, all day.
Refer to the description for Clock 1 [681].
681
Clock 1
6811
Clk1TimeON
Default:
00:00:00 (hh:mm:ss)
Range:
0:00:00–23:59:59
6812
Clk1TimeOff
Default:
00:00:00 (hh:mm:ss)
Range:
0:00:00–23:59:59
6813
Clk1DateOn
Default:
2000-00-00
Range:
yyyy-mm-dd (year-month-day)
6814
Clk1DateOff
Default:
2000-00-00
Range:
yyyy-mm-dd (year-month-day)
6815
Clk1Weekday
Default:
MTWTFSS (all activated)
Range:
Monday, Tuesday, Wednesday, Thursday,
Friday, Saturday, Sunday.
NOTE: Please make sure that the correct time and
date settings are done for the real time clock, menu
group [930] “Clock”.
Menu
Text
Setting
6811
Clk1TimeOn
08:00
6812
Clk1TimeOff
17:00
6813
Clk1DateOn
2017-02-01 (date in the past)
6814
Clk1DateOff
2099-12-31 (Date in the future)
6815
Clk1Weekday
MTWTF- -
561
VIO 1 Dest
Run FWD
562
VIO 1 Source
Clk1
Menu
Text
Setting
6811
Clk1TimeOn
0:00:00
6812
Clk1TimeOff
23:59:59
6813
Clk1DateOn
2017-02-01 (date in the past)
6814
Clk1DateOff
2099-12-31 (Date in the future)
6815
Clk1Weekday
- - - - - SS
561
VIO 1 Dest
Run FWD
562
VIO 1 Source
Clk1
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......