154
CG Drives & Automation 01-7491-01r0
AnIn1 Advanced [513]
Parameter to set the minimum value of the external
reference signal. Only visible if [512] = User mA/V.
AnIn1 Max [5132]
Parameter to set the maximum value of the external
reference signal. Only visible if [512] = User mA/V.
Special function: Inverted reference signal
If the AnIn minimum value is higher than the AnIn
maximum value, the input will act as an inverted reference
input, see fig. 133.
Fig. 133 Inverted reference
This menu is only displayed if AnIn1 Setup is set to User
Bipol mA or User Bipol V. The window will
automatically show mA or V range according to selected
function. The range is set by changing the positive
maximum value; the negative value is automatically adapted
accordingly. Only visible if [512] = User Bipol mA/V. The
inputs RunR and RunL input need to be active, and
“Rotation [219]”, must be set to “R+L”, to operate the
bipolar function on the analogue input.
With AnIn1 Function Min the physical minimum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511].
Table 35 shows corresponding values for the min and max
selections depending on the function of the analogue input
[511].
AnIn1 Function Value Min [5135]
With AnIn1 Function ValMin you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5134].
NOTE: The different menus will automatically be set
to either “mA” or “V”, based on the selection in AnIn 1
Setup [512].
513
AnIn1 Advan
5131
AnIn1 Min
Default:
0 V/4.00 mA
Range:
0.00–20.00 mA
0–10.00 V
5132
AnIn1 Max
Default:
10.00 V/20.00 mA
Range:
0.00–20.00 mA
0–10.00 V
0
1 0 V
100 %
n
(NG_06-F25)
Invert
Ref
AnIn Min >
AnIn Max
5133
AnIn1 Bipol
Default:
10.00 V/20.00 mA
Range:
0.0–20.0 mA, 0.00–10.00 V
5134
AnIn1 FcMin
Default:
Min
Min
0
Min value
Max
1
Max value
User
defined
2
Define user value in menu [5135]
Table 35
AnIn Function
Min
Max
Speed
Min Speed [341]
Max Speed [343]
Torque
0%
Max Torque [351]
Process Ref
Process Min [324]
Process Max [325]
Process Value
Process Min [324]
Process Max [325]
5135
AnIn1 VaMin
Default:
0.000
Range:
-10000.000 – 10000.000
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......