Functional description
CG Drives & Automation 01-7491-01r0
Remote Signal Level/Edge [21A]
In this menu you select the way to control the inputs for
RunR, RunL and Reset that are operated via the digital
inputs on the terminal strip. The inputs are default set for
level-control, and will be active as long as the input is made
and kept high. When edge-control is selected, the input will
be activated by the low to high transition of the input. See
chapter 7.2 Remote control functions page 65 for more
information.
In this menu the nominal mains supply voltage connected to
the AC drive can be selected. The setting will be valid for all
parameter sets. The default setting, Not defined, is never
selectable and is only visible until a new value is selected.
This menu specifies the AC supply voltage. The
corresponding DC voltage is 1.34 times higher.
Once the supply voltage is set, this selection will not be
affected by the Load Default command [243].
Brake chopper activation level is adjusted using the setting
of [21B].
Supply Type [21C]
Set supply voltage type.
When changing to / from the “AFE Supply” selection, the
following parameters are set to following values:
21A
Level/Edge
Default:
Level
Level
0
The inputs are activated or deactivated
by a continuous high or low signal. Is
commonly used if, for example, a PLC is
used to operate the AC drive.
Edge
1
The inputs are activated by a transition;
for Run and Reset from “low” to “high”
and for Stop from "high" to "low".
CAUTION!
Level controlled inputs DO NOT comply with
the Machine Directive if the inputs are
directly used to start and stop the machine.
NOTE: Edge controlled inputs can comply with the
Machine Directive (see the chapter 8. EMC and
standards page 79) if the inputs are directly used to
start and stop the machine.
WARNING!
This menu must be set according to the
AC drive product label and the supply
voltage used. Wrong setting might damage
the AC drive or brake resistor.
NOTE: The setting is affected by the “Load from CP”
command [245] and if loading parameter file via
EmoSoftCom.
!
21B
Supply Volts
Default:
Not defined
Not Defined
0
Inverter default value used. Only valid if
this parameter is never set.
220-240 VAC 1
Only valid for FDU48/52
380-415 VAC 3
Only valid for FDU48/52/69
440-480 VAC 4
Only valid for FDU48/52/69
500-525 VAC 5
Only valid for FDU52/69
550-600 VAC 6
Only valid for FDU69
660-690 VAC 7
Only valid for FDU69
21C
Supply Type
Default:
AC Supply
AC Supply
0
Normal AC supply
AFE Supply
1
DC supply voltage by AFE
DC Supply
2
DC supply voltage
AC/DC Suppl
3
AC/DC supply voltage
Menu
to AFE
from AFE
[523] DigIn 3
Sleep
Off
[542] DigOut 3
Run
Brake
[527] DigIn 7
Off
Off
[561] VIO 1 Dest
External Trip
Off
[562] VIO 1 Source
!D1
Off
[6151] CD 1
DigIn 7
Run
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......