226
Technical Data
CG Drives & Automation 01-7491-01r0
14.8 Control signals
Table 68
Terminal X1
Name:
Function (Default):
Signal:
Type:
1
+10 V
+10 VDC Supply voltage
+10 VDC, max 10 mA
output
2
AnIn1
Process reference
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
3
AnIn2
Off
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
4
AnIn3
Off
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
5
AnIn4
Off
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
6
-10 V
-10VDC Supply voltage
-10 VDC, max 10 mA
output
7
Common
Signal ground
0 V
output
8
DigIn 1
RunL
0-8/24 VDC
digital input
9
DigIn 2
RunR
0-8/24 VDC
digital input
10
DigIn 3
Off
0-8/24 VDC
digital input
11
+24 V
+24VDC Supply voltage
+24 VDC, 100 mA
output
12
Common
Signal ground
0 V
output
13
AnOut 1
Min speed to max speed
0 ±10 VDC or 0/4– +20 mA
analogue output
14
AnOut 2
0 to max torque
0 ±10 VDC or 0/4– +20 mA
analogue output
15
Common
Digital signal ground
0 V via ferrite
output
16
DigIn 4
Off
0-8/24 VDC
digital input
17
DigIn 5
Off
0-8/24 VDC
digital input
18
DigIn 6
Off
0-8/24 VDC
digital input
19
DigIn 7
Off
0-8/24 VDC
digital input
20
DigOut 1
Ready
24 VDC, 100 mA
digital output
21
DigOut 2
No trip
24 VDC, 100 mA
digital output
22
DigIn 8
RESET
0-8/24 VDC
digital input
A+
RS-485 transmit and receive signals
Isolated differential signals -7V to
12V
Communication
B-
Terminal X2
31
N/C 1
Relay 1 output
Trip, active when the
AC drive is in a TRIP condition
N/C is opened when the relay is
active (valid for all relays)
N/O is closed when the relay is active
(valid for all relays)
potential free change over
0.1 – 2 A
U
max
= 250 VAC or 42 VDC
relay output
32
COM 1
33
N/O 1
41
N/C 2
Relay 2 Output
Run, active when the
AC drive is started
potential free change over
0.1 – 2 A
U
max
= 250 VAC or 42 VDC
relay output
42
COM 2
43
N/O 2
Terminal X3
51
COM 3
Relay 3 Output
Off
potential free change over
0.1 – 2 A
U
max
= 250 VAC or 42 VDC
relay output
52
N/O 3
Teminal X11
+
24 VDC±10% Input from 24 VDC ±10% double isolated transformer capable of supplying
1A continues current. Recommended fuse is 2A.
input
-
0 V in
NOTE: Possible potentiometer value in range of 1 kΩ to 10 kΩ (¼ Watt) linear, where we advice to use a
linear 1 kΩ / ¼ W type potentiometer for best control linearity.
Содержание FDU Series
Страница 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 7491 01r0...
Страница 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Страница 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Страница 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Страница 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Страница 195: ...CG Drives Automation 01 7491 01r0 191...
Страница 196: ...192 CG Drives Automation 01 7491 01r0...
Страница 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Страница 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Страница 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Страница 259: ......