background image

7

www.enviromaster.com

The Ductless Split System of Choice

COMMON TO ALL AIR HANDLERS 

Continued

UNITS WITH CONDENSATE PUMPS

EMI Air Handlers are available with an optional conden-

sate pump. Condensate pumps are recommended when it
is not possible to gravity drain the condensation from the
indoor unit. Depending on the pump manufacture the maxi-
mum lift for the pump will vary. Consult the pump instruc-
tions for the maximum lift for the particular pump being used
or refer to specific pump kit information and instructions as
supplied by EMI. (Consult Factory.)

Condensation generated by the evaporator will collect

in the pumps’ reservoir. When the water level is high enough,
a float switch will close and energize the pump motor clear-
ing the water from the reservoir. Should for any reason the
water exceed the maximum preset level, a safety switch
will open, there by interrupting the (Y) signal to the con-
denser. This will prevent the evaporator from generating more
condensation and spilling out of the unit.

EMI may factory install or supply a detailed field instal-

lation kit to follow when pump is purchased as an option
from EMI. (If purchased as an add-on in the field , please
install per manufacturers instructions included with the
pump.

OPTIONAL HEATPUMP WITH

ELECTRIC HEAT 

(2-Stage Heating)

For heat pump operation with backup electric heat, first

turn the unit on via the 

On/off

 button. Select 

Heat

 mode via

the 

Mode

 button. The room temperature will be displayed.

Then, by depressing either the 

Up

 or 

Down

 arrow once, the

setpoint temperature will appear. The setpoint temperature
can then be changed with each successive press of the 

Up

or 

Down

 arrow or by holding the button in.

Place the setpoint temperature one-degree above the

room temperature. The compressor will start and heating
will continue for a minimum of two minutes and as long as
the setpoint remains above room temperature. Once the
room temperature is satisfied and the two-minute minimum
run time has elapsed, the compressor will cycle off.

(*) 

On initial startup (or if power is lost) there is a three-

minute delay between compressor re-starts.

(**) 

Some EMI Heat pump condensers are equipped

with a low temperature cutout that will shut down the con-
denser and energize the indoor heat. This is designed to
protect the compressor under certain outdoor conditions.

Next, place the setpoint temperature at least two de-

grees above room temperature. The electric heat will ener-
gize along with the compressor (heatpump) thus two-stage
heating. The electric heat will continue to run until the de-
viation between room temperature and setpoint tempera-
ture is less than two degrees. At that time the electric heat
will switch off and the heatpump will take over the heating
demand. Once the room temperature is satisfied and the
two-minute minimum run time has elapsed, the compres-
sor will cycle off. There is then a three-minute delay before
the compressor can restart. The fan will operate as described
in “Fan Operation”

 

(

Figure 5)

.

DRY MODE OPERATION

Dry mode will remove humidity from the air while main-

taining a specific setpoint temperature. This is done by en-
ergizing the compressor in cooling along with the electric or
hydronic heater. Dry mode 

will not

 maintain a specific hu-

midity level. The unit must be equipped with an optional
electric heat element or hydronic coil.

For Dry Mode operation first turn the unit on via the 

On/

off

  button. Select 

Dry 

mode via the 

Mode

 button. The room

temperature will be displayed. Then by depressing either
the 

Up

 or 

Down

 arrow once, the setpoint temperature will

appear. The setpoint temperature can then be changed with
each successive press of the 

Up

 or 

Down

 arrow or by hold-

ing the button in.

Place the setpoint temperature at a desired room tem-

perature. Depending on the difference between room tem-
perature and set point temperature the compressor and/or
heat source will energize. If the room temperature and
setpoint temperature are the same the compressor will op-
erate in cooling and the electric heat source will also ener-
gize.

Should the room temperature fall below the setpoint tem-

perature by two degrees, the compressor will stop and heat-
ing will continue to boost the room temperature back up to
stepoint temperature. If the room temperature rises above
the setpoint temperature by two degrees, heating will stop
and cooling will continue to bring the room temperature back
down to stepoint temperature. The fan will operate continu-
ously at low speed while in Dry Mode.

In order to prevent short cycling the minimum on time

for both cooling and heating is two minutes. The minimum
off time is 3 minutes

 

(

Figure 5)

.

Содержание CCP/CHP

Страница 1: ...review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it func tions properly To obtain technical service or warranty assis tance duri...

Страница 2: ...floor wall or ceiling units and two pipe chilled water fan coil model The air handler offers ease of installation operation and service and can be matched with EMI s SCC SHC single zone condensing uni...

Страница 3: ...dard on FHP FCP WHP WCP and CNR optional on CCP CHP backlit LCD display Adjustable operational range from 55 F to 95 F in one degree increments Anti short cycle compressor protection Minimum compresso...

Страница 4: ...ter lines to ensure they are not in con tact with each other The unit s must be mounted securely and level EMI indoor units do not contain a low volt trans former Low volt power is supplied by a trans...

Страница 5: ...otate between Heat Cool Fan or Dry mode If the dipswitches are set for cooling only off off then Heat and Dry will not be accessible Figure 5 START UP See the Common section of this manual pages 2 8 f...

Страница 6: ...e is satisfied and the two minute minimum run time has elapsed the compressor will cycle off The fan will operate as described in Fan Opera tion Figure 5 NOTE Once the compressor is switched off there...

Страница 7: ...denser and energize the indoor heat This is designed to protect the compressor under certain outdoor conditions Next place the setpoint temperature at least two de grees above room temperature The el...

Страница 8: ...the indoor unit is not equipped with electric or hydronic heat then a single stage heat pump thermostat is adequate FAN OPERATION Some thermostats are equipped with an auto on fan switch When this swi...

Страница 9: ...or fan will switch off after the sixty second purge time has elapsed COMMON TO ALL AIR HANDLERS Continued Units with an optional hydronic heat coil or chilled wa ter coil are also equipped with a free...

Страница 10: ...installed NOTE The FHP utilizes a molded plastic top DO NOT sit or stand on it as you may damage the unit 1 Check equipment for damage before mounting 2 Determine the best location for mounting the un...

Страница 11: ...nd dampers are field supplied The back side has a 4 knockout for a fresh air duct Block the opening during installation to prevent foreign objects from getting into the unit The duct should be install...

Страница 12: ...p units are equipped with a standard air bleeder on the highest point on the unit piping CAUTION Disconnect power when bleeding system Make certain liquid does not contact any electrical com ponents F...

Страница 13: ...8 5 8 I D 30 3 8 5 8 I D 36 42 48 3 8 7 8 5 8 I D Model Drain Hose Refrigerant Line Size FHP Shipping Wt Model LBS 9 12 15 110 18 24 30 120 36 42 48 165 FCP FHP Fresh Air Specifications Model Total CF...

Страница 14: ...ptional mounting o o o o FHP 36 48 FHP 36 48 Motorized Damper and Power Assisted Fresh Air 4 Fan Type Wall Box Dimensions 14 from finished floor level x 32 wide x 8 deep FHP 09 30 Motorized Damper and...

Страница 15: ...e the cardboard template provided with unit packing to test fit the unit before installation 1 The CCP CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Us...

Страница 16: ...i s n e S y t i c a p a C d i u l F p m e T d i u l F w o l F i s P D P 2 1 9 0 P C C 0 0 9 7 0 0 9 0 1 0 0 3 3 1 0 0 3 7 0 0 8 8 0 0 8 9 5 4 5 4 5 4 0 1 0 2 0 3 0 3 3 5 8 8 0 0 0 9 0 0 7 2 1 0 0 6 5...

Страница 17: ...backing between the unit and the block surface to absorb any potential vibration IMPORTANT If excessive noise or vibration is ex perienced from a unit mounted directly to a block wall the squareness...

Страница 18: ...gh one of two 7 8 knockout holes A terminal block marked with L1 and L2 and a ground lug are provided 2 Low voltage wiring EMI requires 18 awg low voltage interconnect wiring must be run to the outdoo...

Страница 19: ...TS HZ PH ELECTRIC HEAT INDOOR FAN 1 INDOOR FAN 2 TOTAL AMPS DISCHARGE AIR SPEED AND FLOW LOW HIGH LOW HIGH LOW HIGH DRY 335 370 700 750 10 12 FPM THROW FT CFM COIL 1 4 1 2 INTERCONNECTING REFRIGERANT...

Страница 20: ...r circulation Locate outdoor and indoor units as close together as possible Determine how refrigerant and power line may be run to and from unit Determine if the cabinet front can be removed with out...

Страница 21: ...Wt 09 12 36 14 10 32 9 24 8 18 16 85 15 18 47 14 10 32 10 34 8 18 27 115 24 30 57 14 10 42 10 44 8 27 28 115 36 57 17 11 42 10 44 10 25 28 115 A B C D E 2 2 1 G I F H Wall Mount Bracket Slot for Brack...

Страница 22: ...6 3 8 7 8 Refrigerent Line Size Chilled Line Size I D WHP Suction Connection is 3 4 O D and must be bushed down at the WHP Unit WCP WHP CONNECTIONS WHP s ONLY WCP ELECTRICAL SPECIFICATIONS FLA HP 09A...

Страница 23: ...volt age Also the incoming power should not be below the mini mum voltage stated on the rating plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should al...

Страница 24: ...in the control box As a safety feature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur E...

Страница 25: ...at rating The following current values apply when the unit is con nected to a 230V power supply These values include in door fan motor current 7KW 31 0 AMPS 5KW 22 3 AMPS 3KW 13 5 AMPS Units with elec...

Страница 26: ...ll amount of flickering of the display is normal Depending on the room lighting flickering may be more noticeable at some times than others Q How long will the fan run A While the unit is in cooling o...

Страница 27: ...tor Volts ID Fan Motor Amps Total Volts Total Amps Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Evaporator DB Temp Split at evap Compressor Superheat Sub...

Страница 28: ...other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequenc...

Отзывы: