13
www.enviromaster.com
The Ductless Split System of Choice
FCP/FHP Hydronic Heat Specifications
(Single-stage Heating only)
Model#
EWT °F
Btuh
GPM
PD (PSI)
180
24,300
2
3.4
140
18,400
2
3.4
180
41,500
3.5
5.6
140
26,200
3.5
5.6
180
62,400
6
8.8
140
39,500
6
8.8
NOTE
: Not available w ith Heat Pump applications.
9, 12, 15
18, 24, 30
36, 42, 48
FCP/FHP Electric Heat Specifications
9, 12, 15
230
3
13.1
13.7
17.1
20
18, 24
230
5
21.7
22.7
28.2
30
30
230
5
21.7
22.8
28.6
30
36, 42, 48
230
7
30.4
32.6
40.6
45
Total
Amps
Min. Circuit
Amps
Max. Fuse
Amps
Model#
Voltage
KW
Heater
Amps
FHP Piping Specifications
Liquid
Suction
9, 12
¼"
½"
½" I.D.
15
¼"
5
/
8
"
5
/
8
" I.D.
18
3
/
8
"
5
/
8
"
5
/
8
" I.D.
24
3
/
8
"
¾"
5
/
8
" I.D.
30
3
/
8
"
¾"
5
/
8
" I.D.
36, 42, 48
3
/
8
"
7
/
8
"
5
/
8
" I.D.
Model#
Drain
Hose
Refrigerant Line Size
FHP Shipping Wt.
Model#
LBS.
9, 12, 15
110
18, 24, 30
120
36, 42, 48
165
FCP/FHP Fresh Air Specifications*
Model#
Total CFM Outside Air CFM
9, 12, 15
440
50
18, 24, 30
725
75
36, 42, 48
1200
160
* Open or Motorized Damper
NOTE: Due to EMI’s ongoing development programs, designs and specifications may change without notice.
(FCP/FHP) DIMENSIONS AND SPECIFICATIONS
Continued
26”
10
1
/
2
”
47” (09-30), 61
1
/
2
” (36-48)
FHP’s ONLY
FCP/FHP Electrical Specifications
Model#
Voltage/Hz/Ph
Fan
FLA
Min.
Ampacity*
Max.
Fuse*
9, 12A
115/60/1
1.5
1.9
15
9, 12, 15
208-230/60/1
0.6
0.8
15
18, 24
208-230/60/1
0.8
1
15
30
208-230/60/1
1.1
1.4
15
36, 42, 48 208-230/60/1 1.1/1.1
2.5
15
(*) If electric heat is installed, use data from
FHP Electric Heat Specifications
table.
Hydronic Coil
Location
Hydronic Coil
Evaporator Coil