background image

2

E-mail: [email protected]

Made in Rome, New York, USA

SAFETY INSTRUCTIONS

Read all instructions before using the EMI Air Han-

dler.  Install or locate this unit only in accordance with
these instructions.  Use this unit only for its intended
purpose as described in this manual.

• Check the rating plate on the EMI Air Handler

before installation to make certain the voltage
shown is the same as the electrical supply to
the unit.

• The EMI Air Handler must be connected to a

properly grounded electrical supply.  Do not fail
to properly ground this unit.

• Turn off the electrical supply before servicing the

EMI Air Handler.

• Do not use the EMI Air Handler if it has dam-

aged wiring, is not working properly, or has been
damaged or dropped.

[Save these instructions]

COMMON TO ALL AIR HANDLERS

INSTALLER RESPONSIBILITIES

This manual has been prepared to acquaint you with

the installation, operation, and maintenance of this EMI Air
Handler and to provide important safety information in these
areas.

We urge you to read all of the instructions thoroughly

before attempting the installation or operation of this unit.
This manual should be kept for future reference.

The manufacturer of this unit will not be liable for any

damages caused by failure to comply with the installation
and operating instructions outlined in this manual.

A rating plate identifying this EMI Air Handler can be

found on the unit.  When referring to your unit, always have
the information listed on the rating plate readily available.

Completely read all instructions prior to assem-

bling, installing, operating, or repairing this prod-
uct.  Inspect all parts for damage prior to installa-
tion and start-up.  The EMI Air Handler must be in-
stalled only by qualified installation personnel.

THE EMI AIR HANDLER FAMILY

The EMI Air Handler is available as a Dx direct expan-

sion straight cool, heat pump – floor, wall, or ceiling units –
and  two-pipe chilled water fan coil model.  The air handler
offers ease of installation, operation, and service, and can
be matched with EMI’s SCC/SHC single-zone condensing
unit or either of the company’s multi-zone outdoor units,
the MC2/MH2 or MC4/MH4. Presently, EMI does not offer a
chiller unit that provides chilled water for the FCP, WCP and
CCP models.

NOTE:  Floor and ceiling units in 42,000 Btuh or
48,000 Btuh capacities must be matched with EMI’s
CCB/CHD condense
r.

All EMI Air Handlers are subject to ongoing product de-

velopment so designs and specifications may change with-
out notice.  For more information on a specific air handler,
please refer to the corresponding section in this installation
manual or, for information on EMI Condensing Units, please
visit our website at www.enviromaster.com or contact the
factory for the appropriate literature.

THE EMI DUCTLESS SPLIT SYSTEM AIR

HANDLER FAMILY CONSISTS OF

• 

FCP:  

Two-pipe chilled water fan coil floor unit avail-

able in 9,000, 12,000, 18,000, 24,000, 30,000,
36,000, 42,000, and 48,000 nominal Btuh capacities.

• 

FHP:

  Dx straight cool/heat pump floor unit, avail-

able in 9,000, 12,000, 15,000, 18,000, 24,000,
30,000, 36,000, 42,000, and 48,000 nominal Btuh
capacities.

• 

WCP: 

Two-pipe chilled water fan coil wall unit avail-

able in 9,000, 12,000, 15,000, 18,000, 24,000, and
30,000 nominal Btuh capacities.

• 

WHP:

 Dx straight cool/heat pump wall unit available

in 9,000, 12,000, 15,000, 18,000, 24,000, 30,000,
and 36,000 nominal Btuh capacities.

• 

CNR: 

Dx

 

Straight cool/heat pump corner unit avail-

able in 9,000, and 12,000 nominal Btuh capacities.

• 

CCP:

  Two-pipe chilled water fan coil ceiling unit avail-

able in 9,000, 12,000, 18,000, 24,000, 30,000,
36,000, 42,000, and 48,000 nominal Btuh capaci-
ties.

• 

CHP: 

Dx

 

Straight cool/heat pump floor unit available

in 9,000, 12,000, 15,000, 18,000, 24,000, 30,000,
36,000, 42,000, and 48,000 nominal Btuh capaci-
ties.

All EMI Air Handlers are backed by Enviromaster In-

ternational LLC and are tested and rated in accor-
dance with ARI standards 210/240 and UL 1995.

!

!

WARNING

!

!

DANGER

Содержание CCP/CHP

Страница 1: ...review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it func tions properly To obtain technical service or warranty assis tance duri...

Страница 2: ...floor wall or ceiling units and two pipe chilled water fan coil model The air handler offers ease of installation operation and service and can be matched with EMI s SCC SHC single zone condensing uni...

Страница 3: ...dard on FHP FCP WHP WCP and CNR optional on CCP CHP backlit LCD display Adjustable operational range from 55 F to 95 F in one degree increments Anti short cycle compressor protection Minimum compresso...

Страница 4: ...ter lines to ensure they are not in con tact with each other The unit s must be mounted securely and level EMI indoor units do not contain a low volt trans former Low volt power is supplied by a trans...

Страница 5: ...otate between Heat Cool Fan or Dry mode If the dipswitches are set for cooling only off off then Heat and Dry will not be accessible Figure 5 START UP See the Common section of this manual pages 2 8 f...

Страница 6: ...e is satisfied and the two minute minimum run time has elapsed the compressor will cycle off The fan will operate as described in Fan Opera tion Figure 5 NOTE Once the compressor is switched off there...

Страница 7: ...denser and energize the indoor heat This is designed to protect the compressor under certain outdoor conditions Next place the setpoint temperature at least two de grees above room temperature The el...

Страница 8: ...the indoor unit is not equipped with electric or hydronic heat then a single stage heat pump thermostat is adequate FAN OPERATION Some thermostats are equipped with an auto on fan switch When this swi...

Страница 9: ...or fan will switch off after the sixty second purge time has elapsed COMMON TO ALL AIR HANDLERS Continued Units with an optional hydronic heat coil or chilled wa ter coil are also equipped with a free...

Страница 10: ...installed NOTE The FHP utilizes a molded plastic top DO NOT sit or stand on it as you may damage the unit 1 Check equipment for damage before mounting 2 Determine the best location for mounting the un...

Страница 11: ...nd dampers are field supplied The back side has a 4 knockout for a fresh air duct Block the opening during installation to prevent foreign objects from getting into the unit The duct should be install...

Страница 12: ...p units are equipped with a standard air bleeder on the highest point on the unit piping CAUTION Disconnect power when bleeding system Make certain liquid does not contact any electrical com ponents F...

Страница 13: ...8 5 8 I D 30 3 8 5 8 I D 36 42 48 3 8 7 8 5 8 I D Model Drain Hose Refrigerant Line Size FHP Shipping Wt Model LBS 9 12 15 110 18 24 30 120 36 42 48 165 FCP FHP Fresh Air Specifications Model Total CF...

Страница 14: ...ptional mounting o o o o FHP 36 48 FHP 36 48 Motorized Damper and Power Assisted Fresh Air 4 Fan Type Wall Box Dimensions 14 from finished floor level x 32 wide x 8 deep FHP 09 30 Motorized Damper and...

Страница 15: ...e the cardboard template provided with unit packing to test fit the unit before installation 1 The CCP CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Us...

Страница 16: ...i s n e S y t i c a p a C d i u l F p m e T d i u l F w o l F i s P D P 2 1 9 0 P C C 0 0 9 7 0 0 9 0 1 0 0 3 3 1 0 0 3 7 0 0 8 8 0 0 8 9 5 4 5 4 5 4 0 1 0 2 0 3 0 3 3 5 8 8 0 0 0 9 0 0 7 2 1 0 0 6 5...

Страница 17: ...backing between the unit and the block surface to absorb any potential vibration IMPORTANT If excessive noise or vibration is ex perienced from a unit mounted directly to a block wall the squareness...

Страница 18: ...gh one of two 7 8 knockout holes A terminal block marked with L1 and L2 and a ground lug are provided 2 Low voltage wiring EMI requires 18 awg low voltage interconnect wiring must be run to the outdoo...

Страница 19: ...TS HZ PH ELECTRIC HEAT INDOOR FAN 1 INDOOR FAN 2 TOTAL AMPS DISCHARGE AIR SPEED AND FLOW LOW HIGH LOW HIGH LOW HIGH DRY 335 370 700 750 10 12 FPM THROW FT CFM COIL 1 4 1 2 INTERCONNECTING REFRIGERANT...

Страница 20: ...r circulation Locate outdoor and indoor units as close together as possible Determine how refrigerant and power line may be run to and from unit Determine if the cabinet front can be removed with out...

Страница 21: ...Wt 09 12 36 14 10 32 9 24 8 18 16 85 15 18 47 14 10 32 10 34 8 18 27 115 24 30 57 14 10 42 10 44 8 27 28 115 36 57 17 11 42 10 44 10 25 28 115 A B C D E 2 2 1 G I F H Wall Mount Bracket Slot for Brack...

Страница 22: ...6 3 8 7 8 Refrigerent Line Size Chilled Line Size I D WHP Suction Connection is 3 4 O D and must be bushed down at the WHP Unit WCP WHP CONNECTIONS WHP s ONLY WCP ELECTRICAL SPECIFICATIONS FLA HP 09A...

Страница 23: ...volt age Also the incoming power should not be below the mini mum voltage stated on the rating plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should al...

Страница 24: ...in the control box As a safety feature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur E...

Страница 25: ...at rating The following current values apply when the unit is con nected to a 230V power supply These values include in door fan motor current 7KW 31 0 AMPS 5KW 22 3 AMPS 3KW 13 5 AMPS Units with elec...

Страница 26: ...ll amount of flickering of the display is normal Depending on the room lighting flickering may be more noticeable at some times than others Q How long will the fan run A While the unit is in cooling o...

Страница 27: ...tor Volts ID Fan Motor Amps Total Volts Total Amps Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Evaporator DB Temp Split at evap Compressor Superheat Sub...

Страница 28: ...other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequenc...

Отзывы: