background image

17

www.enviromaster.com

The Ductless Split System of Choice

DESCRIPTION

EMI’s corner mounted air handler (CNR) is revolution-

ary in its state-of-the-art design as a ductless evaporator
that can be mounted inconspicuously in the corner of most
any room.  Using mounting holes on the unit that are set up
to align with any wall construction (including walls with non-
square corners), the CNR utilizes previously unused wall
space for effective high efficiency room conditioning with
whisper quiet operation.

The CNR is equipped with unit mounted infrared com-

patible controls and can easily be installed in small to mid-
size commercial or residential spaces by one person using
the supplied positioning bracket.  Heat pump models pro-
vide up to a nominal 12,000 Btuh of cooling/heating and a
3KW electric heat option is available.  Other design fea-
tures include dual supply airflow and versatility of tubing
and wiring access through multiple entrances on the unit.

OPTIONAL EQUIPMENT

• Integral condensate pump
• Hand held infrared controller
• Wall mounted thermostat control
• 3KW electric heat with automatic reset high tem-

perature cutout

• Temperature fuse link
• Top trim kit for finished look between unit and ceiling
• 24V transformer (see below)

ITEMS FOR CONSIDERATION

• EMI’s CNR evaporator requires 24V power for con-

trol operation.  When matching the CNR with a non-
EMI condenser, a 24V transformer may need to be
added to the condenser.

• Ensure that the CNR interconnect tubing is within a

maximum allowable length of 100’ including, a maxi-
mum 35’ lift.

CORNER MOUNTED AIR HANDLER

(CNR)

UNIT MOUNTING

It is recommended that the CNR be mounted 3" from

the ceiling, allowing proper access to the components located
in the top of the unit.  The CNR must be mounted plumb and
level to a vertically square surface to prevent unit vibration
and/or unwanted noise.  It is recommended that the unit be
mounted directly to a smooth surface of sheetrock wallboard
or similar material.  If mounting to a block wall, there should
be a smooth square backing between the unit and the block
surface to absorb any potential vibration.

IMPORTANT:  If excessive noise or vibration is ex-
perienced from a unit mounted directly to a block
wall, the squareness of the wall should be checked
immediately.

With the CNR, tubing, electrical, and drain access may

be acquired through either the bottom left or right sides or
the top of the unit.  Keep in mind when routing through the
top of the unit through a ceiling that there is a 2 ½” knockout
provided in the top panel for this access.  If you are using
only the top tubing access it will be necessary to install a
condensate pump.

NOTE: An optional top trim kit is available for con-
cealing tubing and/or wiring run through the top of
the unit. In addition, this kit may be used to pro-
vide a finished look between the unit and the ceil-
ing.  To effectively use the top trim kit, the CNR
must be mounted 3" from the ceiling.

Piping may be roughed in before wallboard or panels

are placed in new construction.  PVC (3” or 4" I.D.) may be
used as a pipe chase.

After determining the best location for the unit, use the

right and left paper wall-mounting templates included with
this instruction manual for proper unit mounting.  After ad-
hering the right and left templates to the wall at the proper
height (3" from ceiling), these templates will be used to center
mark and pre-drill necessary holes indicated on the tem-
plates.  Once the holes are drilled, mark/cut holes for tub-
ing and electrical access and remove the templates from
the walls.  The Installer will determine if wall anchors are
necessary.

Included with the CNR is a mounting hardware kit con-

sisting of two 5/16 x 4" lag screws/washers, six #12 x 1-1/4"
Phillips head screws/washers, and six #12 wall anchors.
Use two #12 x 1-1/4" Phillips head screws and wall anchors
to secure the positioning bracket in place on the wall ac-
cording to the proper hole location indicated on the tem-
plates.  The positioning bracket is provided for temporarily
hanging the unit at the proper height.  Use a ¼” drill for
drilling holes for the anchors supplied for sidewall and posi-
tioning bracket mounting.  It is not necessary to use the
remaining wall anchors for sidewalls if mounting directly to
the wall studs.

Содержание CCP/CHP

Страница 1: ...review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it func tions properly To obtain technical service or warranty assis tance duri...

Страница 2: ...floor wall or ceiling units and two pipe chilled water fan coil model The air handler offers ease of installation operation and service and can be matched with EMI s SCC SHC single zone condensing uni...

Страница 3: ...dard on FHP FCP WHP WCP and CNR optional on CCP CHP backlit LCD display Adjustable operational range from 55 F to 95 F in one degree increments Anti short cycle compressor protection Minimum compresso...

Страница 4: ...ter lines to ensure they are not in con tact with each other The unit s must be mounted securely and level EMI indoor units do not contain a low volt trans former Low volt power is supplied by a trans...

Страница 5: ...otate between Heat Cool Fan or Dry mode If the dipswitches are set for cooling only off off then Heat and Dry will not be accessible Figure 5 START UP See the Common section of this manual pages 2 8 f...

Страница 6: ...e is satisfied and the two minute minimum run time has elapsed the compressor will cycle off The fan will operate as described in Fan Opera tion Figure 5 NOTE Once the compressor is switched off there...

Страница 7: ...denser and energize the indoor heat This is designed to protect the compressor under certain outdoor conditions Next place the setpoint temperature at least two de grees above room temperature The el...

Страница 8: ...the indoor unit is not equipped with electric or hydronic heat then a single stage heat pump thermostat is adequate FAN OPERATION Some thermostats are equipped with an auto on fan switch When this swi...

Страница 9: ...or fan will switch off after the sixty second purge time has elapsed COMMON TO ALL AIR HANDLERS Continued Units with an optional hydronic heat coil or chilled wa ter coil are also equipped with a free...

Страница 10: ...installed NOTE The FHP utilizes a molded plastic top DO NOT sit or stand on it as you may damage the unit 1 Check equipment for damage before mounting 2 Determine the best location for mounting the un...

Страница 11: ...nd dampers are field supplied The back side has a 4 knockout for a fresh air duct Block the opening during installation to prevent foreign objects from getting into the unit The duct should be install...

Страница 12: ...p units are equipped with a standard air bleeder on the highest point on the unit piping CAUTION Disconnect power when bleeding system Make certain liquid does not contact any electrical com ponents F...

Страница 13: ...8 5 8 I D 30 3 8 5 8 I D 36 42 48 3 8 7 8 5 8 I D Model Drain Hose Refrigerant Line Size FHP Shipping Wt Model LBS 9 12 15 110 18 24 30 120 36 42 48 165 FCP FHP Fresh Air Specifications Model Total CF...

Страница 14: ...ptional mounting o o o o FHP 36 48 FHP 36 48 Motorized Damper and Power Assisted Fresh Air 4 Fan Type Wall Box Dimensions 14 from finished floor level x 32 wide x 8 deep FHP 09 30 Motorized Damper and...

Страница 15: ...e the cardboard template provided with unit packing to test fit the unit before installation 1 The CCP CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Us...

Страница 16: ...i s n e S y t i c a p a C d i u l F p m e T d i u l F w o l F i s P D P 2 1 9 0 P C C 0 0 9 7 0 0 9 0 1 0 0 3 3 1 0 0 3 7 0 0 8 8 0 0 8 9 5 4 5 4 5 4 0 1 0 2 0 3 0 3 3 5 8 8 0 0 0 9 0 0 7 2 1 0 0 6 5...

Страница 17: ...backing between the unit and the block surface to absorb any potential vibration IMPORTANT If excessive noise or vibration is ex perienced from a unit mounted directly to a block wall the squareness...

Страница 18: ...gh one of two 7 8 knockout holes A terminal block marked with L1 and L2 and a ground lug are provided 2 Low voltage wiring EMI requires 18 awg low voltage interconnect wiring must be run to the outdoo...

Страница 19: ...TS HZ PH ELECTRIC HEAT INDOOR FAN 1 INDOOR FAN 2 TOTAL AMPS DISCHARGE AIR SPEED AND FLOW LOW HIGH LOW HIGH LOW HIGH DRY 335 370 700 750 10 12 FPM THROW FT CFM COIL 1 4 1 2 INTERCONNECTING REFRIGERANT...

Страница 20: ...r circulation Locate outdoor and indoor units as close together as possible Determine how refrigerant and power line may be run to and from unit Determine if the cabinet front can be removed with out...

Страница 21: ...Wt 09 12 36 14 10 32 9 24 8 18 16 85 15 18 47 14 10 32 10 34 8 18 27 115 24 30 57 14 10 42 10 44 8 27 28 115 36 57 17 11 42 10 44 10 25 28 115 A B C D E 2 2 1 G I F H Wall Mount Bracket Slot for Brack...

Страница 22: ...6 3 8 7 8 Refrigerent Line Size Chilled Line Size I D WHP Suction Connection is 3 4 O D and must be bushed down at the WHP Unit WCP WHP CONNECTIONS WHP s ONLY WCP ELECTRICAL SPECIFICATIONS FLA HP 09A...

Страница 23: ...volt age Also the incoming power should not be below the mini mum voltage stated on the rating plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should al...

Страница 24: ...in the control box As a safety feature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur E...

Страница 25: ...at rating The following current values apply when the unit is con nected to a 230V power supply These values include in door fan motor current 7KW 31 0 AMPS 5KW 22 3 AMPS 3KW 13 5 AMPS Units with elec...

Страница 26: ...ll amount of flickering of the display is normal Depending on the room lighting flickering may be more noticeable at some times than others Q How long will the fan run A While the unit is in cooling o...

Страница 27: ...tor Volts ID Fan Motor Amps Total Volts Total Amps Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Evaporator DB Temp Split at evap Compressor Superheat Sub...

Страница 28: ...other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequenc...

Отзывы: