background image

3

www.enviromaster.com

The Ductless Split System of Choice

INSTALLER SUPPLIED ITEMS

• Low voltage wiring (18 AWG required)
• Power wiring
• Mounting fasteners (screws, wall anchors, etc.)
• Chilled water, condensate, and refrigerant piping
• Refrigerant (for interconnect charge)

MATERIALS OF CONSTRUCTION

1. Cabinet fabricated of 20-gauge galvanneal steel with

an off-white powder coat matte finish

• Plastic tops, fronts constructed of a high impact

Polystyrene (HIPS) material

2. Discharge grill construction of high temperature Noryl

plastic (WHP/WCP and CNR ONLY)

• Annodized Aluminum discharge grill FHP/FCP &

CHP/CCP

3. Condensate drain pan constructed of anticorrosive

G90U galvanized steel

INSPECTION

Upon receipt of the shipment carefully check the ship-

ment against the bill of lading.  Make sure all the air han-
dlers have been received.  Inspect each unit for damage.
Assure the carrier makes proper notation on the delivery
receipt of all damage identified and that he completes a
Carrier Inspection Report.  Concealed damage must be re-
ported to the carrier within 15 days of receipt of shipment.

ITEMS FOR CONSIDERATION

• Determine the best location for mounting the unit for

room air circulation.  Locate outdoor and indoor units
as close together as possible.

• Determine how power wire (high and low voltage)

condensate drainage, and refrigerant or water sup-
ply piping (for chilled water units) may be run to and
from unit.  Knockouts on the air handler may be used
for this purpose.

• Determine if the air handler can be accessed for ser-

vice without obstruction.

• 

FHP, WHP, CNR, and CHP ONLY:  

Ensure that in-

terconnect tubing is within the maximum allowable
length of 100’ including a maximum 35’ lift.

• Serviceability should be considered when locating

the unit. The cabinet service panels must be able to
be removed without obstruction.

Unit mount control panel - standard on FHP/FCP,

WHP/WCP and CNR (optional on CCP/CHP)

• ¾” backlit LCD display
• Adjustable operational range from 55° F to 95° F (in

one-degree increments)

• Anti-short cycle compressor protection
• Minimum compressor run time
• 60 second fan purge
• Freeze protection
• Audio feedback on control setting changes
• Universal control board for straight cool or heat pump

condenser operation

• Two-stage heating w/optional electric heat and heat

pump condenser

• Fan operation:  Auto (cycling), High and Low (con-

stant)

• Dry Mode (operates cooling and electric heat simul-

taneously to remove humidity when optional electric
heat is selected)

• Test Operation for ease of testing after installation

(all timers eliminated)

• Non-volatile Backup Memory (control settings main-

tained indefinitely during power outages)

IMPORTANT:  Unit mounted controls are fully
functional without the hand-held remote. See page 6

IMPORTANT: 

 

It is the responsibility of the pur-

chaser to file all necessary claims with the carrier.
Notify the Enviromaster International traffic depart-
ment of all damages.

 UNIT MOUNT INFRARED CONTROL

OPERATION

EMI Air Handlers are equipped with a unit mount, infra-

red compatible control package, optional on the CCP/CHP.
This user friendly, microprocessor control is designed to
optimize system performance and protect the refrigeration
system from unwanted short cycling and evaporator freeze-
ups. Operation of the unit can be made by either the key-
pad on the unit or by using the optional hand held infrared
controller.

OPTIONAL CONTROLS/COMPONENTS

• Infrared thermostat with hand held remote for CCP/

CHP

• Condensate Pump (field or factory installed)
• Chilled Water Control Valve (field installed)
• Wiring for normally closed/power open valve (24V

AC, 20VA max. or 8VA max. on units with conden-
sate pumps)

• Open wire electric heaters in all size (all with auto-

matic reset high temperature cutout and redundant
high temperature fuse link)

• Hydronic heat coil with sweat connections (consult

factory) FCP/FHP and CCP/CHP only.

CONTROLS AND COMPONENTS

Factory Installed or Supplied

Содержание CCP/CHP

Страница 1: ...review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it func tions properly To obtain technical service or warranty assis tance duri...

Страница 2: ...floor wall or ceiling units and two pipe chilled water fan coil model The air handler offers ease of installation operation and service and can be matched with EMI s SCC SHC single zone condensing uni...

Страница 3: ...dard on FHP FCP WHP WCP and CNR optional on CCP CHP backlit LCD display Adjustable operational range from 55 F to 95 F in one degree increments Anti short cycle compressor protection Minimum compresso...

Страница 4: ...ter lines to ensure they are not in con tact with each other The unit s must be mounted securely and level EMI indoor units do not contain a low volt trans former Low volt power is supplied by a trans...

Страница 5: ...otate between Heat Cool Fan or Dry mode If the dipswitches are set for cooling only off off then Heat and Dry will not be accessible Figure 5 START UP See the Common section of this manual pages 2 8 f...

Страница 6: ...e is satisfied and the two minute minimum run time has elapsed the compressor will cycle off The fan will operate as described in Fan Opera tion Figure 5 NOTE Once the compressor is switched off there...

Страница 7: ...denser and energize the indoor heat This is designed to protect the compressor under certain outdoor conditions Next place the setpoint temperature at least two de grees above room temperature The el...

Страница 8: ...the indoor unit is not equipped with electric or hydronic heat then a single stage heat pump thermostat is adequate FAN OPERATION Some thermostats are equipped with an auto on fan switch When this swi...

Страница 9: ...or fan will switch off after the sixty second purge time has elapsed COMMON TO ALL AIR HANDLERS Continued Units with an optional hydronic heat coil or chilled wa ter coil are also equipped with a free...

Страница 10: ...installed NOTE The FHP utilizes a molded plastic top DO NOT sit or stand on it as you may damage the unit 1 Check equipment for damage before mounting 2 Determine the best location for mounting the un...

Страница 11: ...nd dampers are field supplied The back side has a 4 knockout for a fresh air duct Block the opening during installation to prevent foreign objects from getting into the unit The duct should be install...

Страница 12: ...p units are equipped with a standard air bleeder on the highest point on the unit piping CAUTION Disconnect power when bleeding system Make certain liquid does not contact any electrical com ponents F...

Страница 13: ...8 5 8 I D 30 3 8 5 8 I D 36 42 48 3 8 7 8 5 8 I D Model Drain Hose Refrigerant Line Size FHP Shipping Wt Model LBS 9 12 15 110 18 24 30 120 36 42 48 165 FCP FHP Fresh Air Specifications Model Total CF...

Страница 14: ...ptional mounting o o o o FHP 36 48 FHP 36 48 Motorized Damper and Power Assisted Fresh Air 4 Fan Type Wall Box Dimensions 14 from finished floor level x 32 wide x 8 deep FHP 09 30 Motorized Damper and...

Страница 15: ...e the cardboard template provided with unit packing to test fit the unit before installation 1 The CCP CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Us...

Страница 16: ...i s n e S y t i c a p a C d i u l F p m e T d i u l F w o l F i s P D P 2 1 9 0 P C C 0 0 9 7 0 0 9 0 1 0 0 3 3 1 0 0 3 7 0 0 8 8 0 0 8 9 5 4 5 4 5 4 0 1 0 2 0 3 0 3 3 5 8 8 0 0 0 9 0 0 7 2 1 0 0 6 5...

Страница 17: ...backing between the unit and the block surface to absorb any potential vibration IMPORTANT If excessive noise or vibration is ex perienced from a unit mounted directly to a block wall the squareness...

Страница 18: ...gh one of two 7 8 knockout holes A terminal block marked with L1 and L2 and a ground lug are provided 2 Low voltage wiring EMI requires 18 awg low voltage interconnect wiring must be run to the outdoo...

Страница 19: ...TS HZ PH ELECTRIC HEAT INDOOR FAN 1 INDOOR FAN 2 TOTAL AMPS DISCHARGE AIR SPEED AND FLOW LOW HIGH LOW HIGH LOW HIGH DRY 335 370 700 750 10 12 FPM THROW FT CFM COIL 1 4 1 2 INTERCONNECTING REFRIGERANT...

Страница 20: ...r circulation Locate outdoor and indoor units as close together as possible Determine how refrigerant and power line may be run to and from unit Determine if the cabinet front can be removed with out...

Страница 21: ...Wt 09 12 36 14 10 32 9 24 8 18 16 85 15 18 47 14 10 32 10 34 8 18 27 115 24 30 57 14 10 42 10 44 8 27 28 115 36 57 17 11 42 10 44 10 25 28 115 A B C D E 2 2 1 G I F H Wall Mount Bracket Slot for Brack...

Страница 22: ...6 3 8 7 8 Refrigerent Line Size Chilled Line Size I D WHP Suction Connection is 3 4 O D and must be bushed down at the WHP Unit WCP WHP CONNECTIONS WHP s ONLY WCP ELECTRICAL SPECIFICATIONS FLA HP 09A...

Страница 23: ...volt age Also the incoming power should not be below the mini mum voltage stated on the rating plate 197V for units rated 208 230V and 104V for units rated 115V A check for low voltage power should al...

Страница 24: ...in the control box As a safety feature an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over heat condition occur E...

Страница 25: ...at rating The following current values apply when the unit is con nected to a 230V power supply These values include in door fan motor current 7KW 31 0 AMPS 5KW 22 3 AMPS 3KW 13 5 AMPS Units with elec...

Страница 26: ...ll amount of flickering of the display is normal Depending on the room lighting flickering may be more noticeable at some times than others Q How long will the fan run A While the unit is in cooling o...

Страница 27: ...tor Volts ID Fan Motor Amps Total Volts Total Amps Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Evaporator DB Temp Split at evap Compressor Superheat Sub...

Страница 28: ...other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequenc...

Отзывы: