52
SI-EtherCAT User Guide
Issue Number: 2
7.3.12
0x6091 Gear_ratio
This object is used to apply scaling. When configured, appropriate user units can be used to control
the position of the shaft beyond a gearbox. The gear ratio is calculated using the following formula:
gear ratio = motor shaft revolutions / driving shaft revolutions
Table 7-24 Gear_ratio
7.3.13
0x6092 Feed_constant
This is used to configure a feed constant. This is the measurement distance per one revolution of
the output shaft of the gearbox. The feed constant is calculated using the following formula:
feed constant = feed / driving shaft revolutions
Table 7-25 Feed_constant
0x6091
Gear_ratio
Sub-index 0
Access: RO
Range: N/A
Size: Unsigned 8
Unit: N/A
Default: 2
Type:
USINT
Description:
Sub-index 1
Access: RW
Range: 0 to 0xFFFFFFFF
Size: Unsigned 32
Unit: N/A
Default: 1
Type:
UDINT
Description: Motor
revolutions
Sub-index 2
Access: RW
Range: 0 to 0xFFFFFFFF
Size: Unsigned 32
Unit: N/A
Default: 1
Type:
UDINT
Description: Shaft
revolutions
0x6092
Feed_constant
Sub-index 0
Access: RO
Range: N/A
Size: Unsigned 8
Unit: N/A
Default: 2
Type:
USINT
Description:
Sub-index 1
Access: RW
Range: 0 to 0xFFFFFFFF
Size: Unsigned 32
Unit: N/A
Default: 1
Type:
UDINT
Description: Feed
Sub-index 2
Access: RW
Range: 0 to 0xFFFFFFFF
Size: Unsigned 32
Unit: N/A
Default: 1
Type:
UDINT
Description: Shaft
revolutions