48
SI-EtherCAT User Guide
Issue Number: 2
7.3.2
0x605A Quick stop option code
This object indicates what action is performed when the quick stop function is executed. The slow
down ramp is the deceleration value of the used mode of operations.
Table 7-8 Quick_stop_option_code
Table 7-9 Quick stop value definitions
7.3.3
0x605B Shutdown_option_code
This object is used to control what action is performed if there is a transition from the Operation
Enabled state to the Ready To Switch On state.
Table 7-10 Shutdown_option_code
Table 7-11 Shutdown_option_code values
7.3.4
0x605C Disable_operation_option_code
Disable drive function (switch off the drive power stage).
This object is used to control what action is performed if there is a transition from the ‘Operation
Enabled’ state to the ‘Switched On’ state.
Table 7-12 Disabled_operation_option_code
0x605A
Quick_stop_option_code
Sub-index 0
Access: RW
Range: 0 to 6
Size: Unsigned 16
Unit: N/A
Default: 2
Type:
UINT
Description:
Specifies what action is performed in the event of a quick stop function. See Table 7-7
state machine transition and events
on page 47 for more information.
Value
Definition
0
Disable drive function
1
Slow down on slow down ramp and transit into Switch on disabled
2
Slow down on quick stop ramp and transit into Switch on disabled
5
Slow down on slow down ramp and stay in Quick stop active
6
Slow down on quick stop ramp and stay in Quick stop active
0x605B
Shutdown_option_code
Sub-index 0
Access: RW
Range: 0 to 1
Size: Unsigned 16
Unit: N/A
Default: N/A
Type:
UINT
Description:
Used to control what action is performed if there is a transition from the Operation Enabled
state to the Ready To Switch On state.
Value
Definition
0
Disable drive function (switch off the drive power stage)
1
Slow down with slow down ramp; disable the drive function
0x605C
Disable_operation_option_code
Sub-index 0
Access: RW
Range: 0 to 1
Size: Unsigned 16
Unit: N/A
Default: N/A
Type:
UINT
Description:
This object is used to control what action is performed if there is a transition from the
Operation Enabled state to the Switched On state.
Содержание SI-EtherCAT