Functional test procedure
Perform a functional test of the detector as described in
.
4.1.3
Keeping maintenance records
Emerson recommends that you record maintenance operations performed on a detector
in a log book. The record should include the following:
•
Installation date and contractor
•
Serial and tag number
•
Entries for every maintenance operation performed, including the description of the
operation, date, and personnel ID
If you send a unit to Rosemount or a distributer for service, include a copy of the
maintenance records.
4.2
Troubleshooting
This section is intended to be a guide to correct problems that may happen during normal
operation.
4.2.1
Fault relay at N.O.
LEDs off
0-20 mA at 0 mA
No power to the unit
Recommended actions
1. Check that the correct power is sent to the detector.
2. Check power polarity.
3. Check wiring in the detector.
4. Send the detector back for repairs.
4.2.2
Fault relay at N.O.
Yellow/amber LED flashes at 4 Hz.
0-20 mA at 0 mA
Detector fault
•
Low voltage
•
Faulty detector
Recommended actions
1. Check the voltage at the detector; verify at least 24 V at the detector terminal.
Maintenance and troubleshooting
Reference Manual
August 2019
00809-0100-4975
44
Emerson.com/Rosemount
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...