Table 1-3: Output Configurations
(continued)
Output
configuration
Connections provided
1R
Power
Manual built-
in test
Fault relay
N.C.
Alarm relay
N.O.
Auxiliary
N.O.
RS-485
N/A
2R
Power
Manual built-
in test
Fault relay
N.O.
Alarm relay
N.O.
Auxiliary
N.O.
RS-485
N/A
NOTICE
Output configuration 1A is default. You can change the mA sink output to source type,
with a link between terminals 1 and 8. You cannot change any other output configurations
on site.
For example, product number 975MR3A8S2A1 has the following options:
•
Output configuration: 3A (analog/HART/RS-485/relays, fault N.O., alarm N.O./N.C.,
source)
•
Housing style: 8S (stainless steel - M25 conduit entry)
•
Temperature: 2 (185 °F [85 °C])
•
Approvals: A1 (ATEX and IECEx flameproof)
NOTICE
Check your specific part numbers against the information in
.
1.3
Features and benefits
The flame detector has the following features and benefits.
•
Detection range: Up to 215 ft. (65 m) for a 1 ft.
2
(0.1 m
2
) n-heptane fire.
•
Ultra high immunity to false alarms. See
.
•
Advanced digital processing of the dynamic characteristics of fire: flickering, threshold,
correlation, and ratio.
•
Multi IR channels: between two and five microns.
•
Field programmable sensitivity: four ranges to avoid zone crossover.
•
Built-in-test (BIT): manual and automatic (see
).
•
Heated window: prevents effects of icing, snow, and condensation.
•
Electrical interface:
—
Dry contact relays
—
Communication network RS-485
—
0-20 mA output
•
HART
®
protocol: communication protocol (see
).
Introduction
Reference Manual
August 2019
00809-0100-4975
10
Emerson.com/Rosemount
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...