3. Wait 20 seconds before repeating the test.
4. Verify that the optical window is clean.
D.1.4
Range
Table D-1: Sensitivity Ranges
Sensitivity
Detection range (ft. / m)
Standard test range (ft. / m)
1 (low)
50 / 15
6.6 / 2
2
100 / 30
19.6 / 6
3
150 / 45
29.5 / 9
4 (high)
215 / 65
39.3 / 12
1. The minimum distance from the detector is 20 in. (50 cm).
2. At extreme temperatures, there is a 15 percent maximum reduction in the range.
NOTICE
Keep the flame simulator in a safe place when not in use.
D.1.5
Charge the battery
The flame simulator uses lithium ion batteries as a rechargeable power source. When the
batteries are fully charged, the simulator operates for at least 1,000 times without having
to be recharged. The simulator will not operate when the voltage from the batteries is
lower than the required operational level.
Figure D-2: Flame Simulator Battery Replacement
A. Simulator
B. Battery pack
C. Locking disc
D. Back cover
Reference Manual
Accessories
00809-0100-4975
August 2019
Rosemount 975MR
63
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...