This product is available to use in hazardous zones 1 and 2 with IIC gas group vapors
present and zones 21 and 22 with IIIC dust type present.
FM, CSA
The flame detector is certified to FM and CSA explosion proof and functionality per
FM3260.
•
Class I, Division 1, Groups B, C, and D, T5 Ta = 85 °C.
•
Dust ignition proof - Class II/III Division 1, Groups E, F, and G.
•
Ingress protection - IP67, IP66, NEMA 250 Type 6P
•
Fuel test response including: gasoline, n-heptane, diesel, JP5, kerosene, ethyl, alcohol
95 percent, IPA, methanol, methane, LPG, polypropylene, and paper.
•
For more details, see
FM Report Project ID3029553
and
.
SIL-2 (TÜV)
The flame detector is certified to SIL-2 requirement per IEC 61508A, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
•
Alert signal via 0-20 mA current loop
or
•
Alert signal via alarm relay and fault relay
For more details and guidelines for configuring, installing, operating, and service, see
.
EN54-10
The flame detector is approved per EN54-10 and CPD.
•
The detector is listed as Class 1 for sensitivity settings 15, 30, 45, and 60.
•
The detector has been tested and approved per EN54-10 Vds.
•
This test includes functional test, environmental test, EMI/EMC test, and software
check.
•
For more details, see Vds Report Number
BMA 150190-AU01+BZA02-PB01
.
InMetro (UL)
The flame detector is in compliance with the following standards as of May 18, 2010:
•
ABNT NBR IEC 60079-0
•
ABNT NBRIEC 60079-1
•
ABNT NBR IEC 60079-7
•
ABNT NBR IEC 60079-18
•
ABNT NBR IEC 60079-31
•
INMETRO decree No. 179
Reference Manual
Introduction
00809-0100-4975
August 2019
Rosemount 975MR
13
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...