Auxiliary relay: No
•
Automatic BIT: Yes
•
Alarm BIT: No
•
Auxiliary BIT: No
•
Heated optics: Auto
•
Temperature: 41 °F (5 °C)
2.8.1
Sensitivity
The detector offers four (4) sensitivity settings. The settings refer to an n-heptane or
gasoline fire of 1 ft.
2
(0.1 m
2
), from the low sensitivity of 50 ft. (15 m) to 215 ft. (65 m).
For other types of fuel sensitivity, refer to
.
2.8.2
Alarm delay
The flame detector is equipped with an alarm delay option, which provides programmable
time delay with settings at:
•
(default)
Other delay settings are available:
•
0, 3, 5, 10, 15, 20, or 30 seconds
When an alarm (detection) level condition occurs, the flame detector delays the execution
of the alarm outputs by the specified period of time. The detector then evaluates the
condition for three seconds. If the alarm level is still present, the detector activates the
alarm outputs. If this condition no longer exists, the detector returns to its standby state.
The alarm delay option affects the output relays and the 0-20 mA output. The LEDs and
outputs indicate warning levels during the delay time only if the fire condition exists.
2.8.3
Address setup
The flame detector provides up to 247 addresses that can be changed with the RS-485
communication link or the HART
®
communication protocol.
2.8.4
Function setup
You can select the desired functions as detailed in
.
Table 2-3: Functions
Function
Setting
Alarm latch
•
Yes: Enable alarm latching.
•
No: Disable alarm latching (default).
(1)
The Antiflare mode is selected to prevent false alarms in locations where fast flares may be present. The time delay for fire
alarms in this mode ranges from 2.5 to 15 seconds (usually less than 10 seconds).
Installing the detector
Reference Manual
August 2019
00809-0100-4975
36
Emerson.com/Rosemount
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...