In a manual built-in test, the outputs may also be tested; apply control system
inhibit
if
this could initiate other systems.
How the built-in test operates
•
The detector's status remains unchanged if the result of a built-in test is the same as
the current status (Normal or BIT Fault).
•
The detector's status is changed (from Normal to BIT Fault or vice versa) if the built-in
test differs from the current status.
NOTICE
In BIT Fault status, the detector can continue to detect a fire.
Automatic built-in test
The detector automatically performs a built-in test every fifteen minutes. A successful
built-in test sequence does not activate any indicator.
All outputs of built-in test results function as described in
, and
the built-in test is automatically executed every one minute.
This continues until a successful built-in test occurs, when the detector resumes normal
operation.
Table 1-12: Results of a Successful Built-in Test
Output
Result
Fault relay
•
Output configurations 1A, 2A, and 1R:
remain CLOSED
•
Output configurations 3A and 2R: remain
OPEN
0-20 mA output
Output configurations 1A, 2A, and 3A: Normal
(4 mA)
Power LED
Green, flashing, 1 Hz on (Normal)
Table 1-13: Results of an Unsuccessful Built-in Test
Output
Result
Fault relay
•
Output configurations 1A, 2A, and 1R:
change to OPEN
•
Output configurations 3A and 2R: change to
CLOSED
0-20 mA output
Output configurations 1A, 2A, and 3A: BIT Fault
(2 mA)
Power LED
Yellow, flashing, 4 Hz
Reference Manual
Introduction
00809-0100-4975
August 2019
Rosemount 975MR
23
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...