This appendix details the special conditions to comply with the requirements of EN 61508
for SIL 2.
The Rosemount 975MR Flame Detector can only be used in low or high demand mode
applications; see IEC 61508.4, Chapter 3.5.12.
E.1
Safety relevant parameters
Perform the following functional checks of the detector.
•
Alternative 1: Functional check of the detector every 180 days:
—
HFT: 0
—
PFD: 3.0 x 10
-4
(≈ 3% of SIL-2) if only alarm relay is used for alerting.
—
PFD: 3.2 x 10
-4
(≈ 3.2% of SIL-2) if 0-20 mA interface is used as alarm.
—
PFH: 1.5 x 10
-7
1/h (≈14.9% of SIL-2) for 0-20 mA application.
—
SFF: 95% fulfills the conditions of EN 61508 for SIL-2.
•
Alternative 2: Functional check of the detector every 365 days:
—
HFT: 0
—
PFD: 4.5 x 10
-4
(≈ 4.5% of SIL-2) if only alarm relay is used for alerting.
—
PFD: 4.9 x 10
-4
(≈ 4.9% of SIL-2) if 0-20 mA interface is used as alarm.
—
PFH: 1.5 x 10
-7
1/h (≈14.9% of SIL-2) for 0-20 mA application.
—
SFF: 95% fulfills the conditions of EN 61508 for SIL-2.
E.2
Guidelines for configuring, installing,
operating, and service
The alert conditions according to SIL-2 can be implemented by an:
•
Alert signal via 20 mA current loop
or
•
Alert signal via alarm relay and the fault relay
E.2.1
Conditions for safe operating
1. The flame detector shall consist only of the approved hardware and software
modules.
2. The 24 V power supply must fulfill the requirements for PELV/SELV of EN 60950.
3. The automatic BIT (built-in test) must be activated.
Reference Manual
SIL-2 features
00809-0100-4975
August 2019
Rosemount 975MR
71
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...