A
Specifications and reference data
A.1
General
A.1.1
Instrument accuracy
± 2.0 mm (0.08 in.)
Instrument accuracy is under reference conditions. Reference conditions are:
Measurement in test bench at Rosemount Tank Radar AB in Mölnlycke Sweden. Test
bench is calibrated minimum yearly by an accredited laboratory (SP Technical Research
Institute of Sweden. Measuring range is up to 30 m (98 ft). Ambient temperature and
humidity is close to constant during tests. Total uncertainty in test bench is below 0.15
mm (0.006 in.).
A.1.2
Temperature stability
Typically < ± 0.5 mm (0.020 in.) in -40 to +70 °C (-40 to +158 °F)
A.1.3
Fieldbus (standard)
F
OUNDATION
™
Fieldbus FISCO (Tankbus)
A.1.4
Update time
New measurement every 0.3 s
A.1.5
Repeatability
0.2 mm (0.008 in.)
A.1.6
Maximum level rate
Up to 200 mm/s
A.1.7
Metrology sealing possibility
Yes
A.1.8
Installation considerations
.
Reference Manual
Specifications and reference data
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
245
Содержание Rosemount 5900C
Страница 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Страница 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Страница 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Страница 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Страница 244: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5901 244 Reference Manual ...
Страница 278: ...Specifications and reference data Reference Manual September 2019 00809 0100 5901 278 Reference Manual ...
Страница 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...