Figure 3-8: Maximum Inclination with Welded Flange
60 mm
< 17°
Nozzle requirements
When installing the Rosemount 5900C with Parabolic Antenna on a 20 inch nozzle, the
nozzle height must not exceed 600 mm (24 in.). There has to be a free passage for the
radar beam within a 5° angle from the edge of the parabolic reflector to the lower end of
the nozzle.
The Rosemount 5900C should be installed so that the distance between flange and
product surface exceeds 800 mm (31 in.). Highest accuracy is obtained for product levels
below this point.
Nozzles with larger diameter may be higher than 600 mm (24 in.) as long as the
requirement of 5° free passage is fulfilled.
Installation
Reference Manual
September 2019
00809-0100-5901
36
Reference Manual
Содержание Rosemount 5900C
Страница 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Страница 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Страница 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Страница 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Страница 244: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5901 244 Reference Manual ...
Страница 278: ...Specifications and reference data Reference Manual September 2019 00809 0100 5901 278 Reference Manual ...
Страница 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...