User Manual
Chapter 4
GFK-2843A
Jan 2020
Assembly, removal, and electrical installation
28
4.2.2
Electrical installation of the safety module
Important
During installation, always observe the instructions in "Electrical safety" on page 2.
Take measures to prevent the incorrect connection, polarity reversal, and manipulation of
connections.
The supply voltages are supplied at a bus coupler and/or a power terminal and are supplied
to the safety module via the potential jumpers. Therefore, the electrical installation of the
safety module only involves connecting the actuators.
The actuators are connected via VersaPoint connectors.
•
Wire the connectors according to your application. For the terminal point
assignment, please refer to "Terminal point assignment" on page 19.
For wiring, proceed as follows:
•
Strip 8 mm off the cable.
Important
VersaPoint wiring is normally done without ferrules. However, it is possible to use
ferrules. If using ferrules, make sure they are properly crimped.
•
Push a screwdriver into the actuation shaft of the appropriate terminal point (Figure
11, detail 1), so that you can insert the wire into the spring opening.
•
Insert the wire (Figure 11, detail 2). Remove the screwdriver from the opening. This
clamps the wire.
Figure 11: Connecting unshielded cables